Inspections for the day of: Thursday, January 10, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00106 Electrical Rough-In1/9/20191/10/20191/10/2019 2:57:37 PMPPASS
Please contact Brian w/any questions or comments

Thank you ; have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Wall rough in ok cover
ELE19-00038 Electrical Rough-In1/9/20191/10/20191/10/2019 2:32:35 PMPFAIL
Elec ri. Zach on site. Phone #: ###-#### Inspection requested via web by Garrett Collins 210.52- A receptacle outlet shall be installed with in 6' of pocket door in master bedroom.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates in kitchen near sink.
314.17(C)- Where knob and tube wiring enter a non-metallic box the conductors shall enter thru individual holes. Kitchen ceiling near door.
334.30- NM calbe shall be secured in place with in 12" of a box. NM cable passes thru hole in beam and enters recessed can with out being secured in place.
House is unoccupied
ELE19-00102 Final1/9/20191/10/20191/10/2019 12:13:20 PMAPASS
Garage code 6975 to access job Phone #: ###-#### Inspection requested via web by Same Electric
Final ok
ELE19-00102 Electrical Rough-In1/10/20191/10/20191/10/2019 11:35:21 AMPPASS
Garage code 6975 to access job Phone #: ###-#### Inspection requested via web by Same Electric
Tesla charger, listing confirmed, rough in ok
ELE18-03640 Final1/9/20191/10/20191/10/2019 11:18:28 AMAPASS
garage code 1524 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE18-03320 Electrical Rough-In1/9/20191/10/20191/10/2019 11:01:42 AMAPART
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
590.6(A)(2)- Trim out temp power part of building power GFCI protection shall be provided during construction. Few plug in GFCI being used, most are not using.
Level 4 grid rough in ok cover. OK for furniture.
ELE19-00020 Final1/9/20191/10/20191/10/2019 10:27:56 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M Final ok
ELE18-02369 Conference1/10/20191/10/20191/10/2019 9:35:29 AMPPASS
Discussed with Ben temporary power requirements for job site. Having issues with tripping circuit taking out multiple floors. As long as temporary power complies with 590.6(B)(1)(2)(3) ok to make changes to reduce tripping issues.