Inspections for the day of: Wednesday, January 16, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02369 Electrical Rough-In1/14/20191/16/20191/16/2019 3:07:17 PMPPASS
1st Floor hardlid areas. Call Joey C. prior to arrival. ###-####. Phone #: ###-#### Inspection requested via web by Scott Campbell Level 1 elevator lobby, clouds, bathrooms hardlids and south stair levels1 to 2 1/2 wall rough in ok cover
ELE19-00127 Electrical Rough-In1/15/20191/16/20191/16/2019 2:43:11 PMPPASS
Inspect underground conduit and light pole bases for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
As noted rough in ok cover
ELE18-02894 Final1/15/20191/16/20191/16/2019 2:05:34 PMPFAIL
Phone #: ###-#### Inspection requested via web by Robert Carter
210.12- All outlets located in bedroom areas shall have GFCI protection.
314.25- All boxes shall have covers. HVAC control switch in hallway.
ELE19-00184 Rough-In Permanent Service1/16/20191/16/20191/16/2019 1:32:44 PMPFAIL
The ceiling in the bottom of the garage stairs will be furred down so its flat, we have 2 can lights and a smoke detector/ CO2 combo going in there when the fur down is done Phone #: ###-#### Inspection requested via web by Bob Glenn
210.52(A)- In habitable rooms no point measured along floor line shall be more than 6' from a receptacle outlet. Up rec room 13' between receptacle outlets.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. Top of house stair in be at floor level marked with X and at bottom of house stair above switches where drill at 45 degree angle.
ELE18-03442 Final1/15/20191/16/20191/16/2019 11:38:23 AMAPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
ELE18-01608 Electrical Rough-In1/15/20191/16/20191/16/2019 10:38:04 AMAPASS
Inspect underground conduit for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
West branch circuit underground rough in ok cover
ELE18-01935 Electrical Rough-In1/15/20191/16/20191/16/2019 9:38:08 AMAPASS
Units 211 , 212 , 213 , 214 , 215 and partials for patio cover units 312 , 314 , 412 , 414 Phone #: ###-#### Inspection requested via web by Tom Betty
Patios only on 312, 314, 412, 414 and full units on other noted rough in ok cover.
ELE18-03393 Final1/15/20191/16/20191/16/2019 8:34:55 AMAPASS
Can we do this one at 7:30? Before clinical staff start work. Phone #: ###-#### Inspection requested via web by Mark M Final ok