Inspections for the day of: Thursday, January 24, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00513 ELE-Aging Inspection1/24/20191/24/20191/25/2019 10:36:43 AM FAIL
No changes
ELE18-04784 Electrical Rough-In1/24/20191/24/20191/24/2019 2:04:28 PMPPASS
Inspect underground conduit Phone #: ###-#### Inspection requested via web by Tom Jenkins
Underground along north fence, allow for repair of damaged 3/4" pvc. rough in ok cover
ELE18-02742 Rough-In Permanent Service1/23/20191/24/20191/24/2019 1:40:26 PMPPASS
inspect service to energize Phone #: ###-#### Inspection requested via web by Mike McCarrel
6011 AIC on a 10k rated main south west service on C-4 building. p/s u/g n ok
ELE19-00030 Electrical Rough-In1/23/20191/24/20191/24/2019 10:48:51 AMAPASS
Underground Rough-In Phone #: ###-#### Inspection requested via web by Bryan Atkins
Underground associated with electrical room rough in ok cover
ELE18-01935 Electrical Rough-In1/23/20191/24/20191/24/2019 10:13:25 AMAPASS
Drop ceilings unit 201 , 202 , 203 Call John Phone #: ###-#### Inspection requested via web by Tom Betty
Areas noted rough in ok cover
ELE18-04755 Final1/23/20191/24/20191/24/2019 9:39:29 AMAFAIL
Joseph Phone #: ###-####
210.8(B)- All 15 or 20 amp 120 volt receptacle outlets located in bathrooms shall have GFCI protection.
Posted correction at same location as building permit.