Inspections for the day of: Wednesday, January 29, 2020.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00014 Rough-In Permanent Service1/29/20201/29/20201/29/2020 3:44:07 PMPPASS
Phone #: ###-#### Inspection requested via web by Dean Gernaat
House only rough in ok cover p/s u/g n ok
ELE20-00014 Electrical Rough-In1/29/20201/29/20201/29/2020 3:43:57 PMPFAIL
Phone #: ###-#### Inspection requested via web by Dean Gernaat
Shop not included in description of building permit.
250.32- Seperate buildings or structure fed by feeders or branch circuits shall have a grounding electrode conductor installed. Concrete encased electrode present with no connection to sub-fed panel.
No access to upstairs of shop.
Feeders to shop not in at time of inspection. Sub-feed in crawl space of house under stairs.
ELE19-04522 Final1/28/20201/29/20201/29/2020 2:45:32 PMPFAIL
It Will Be Ready And Open For Ya Thanks Phone #: ###-#### Inspection requested via web by jason shifflett
406.4(D)(3)- Ground fault circuit interupter protected receptacles shall be provided where replacements are made at receptacle outlets that are required to be so protected elsewhere by code. Garage areas.
406.5(D)- Face plates required for receptacle outlets. Master vanity double duplex.
ELE19-04755 Permanent Service1/29/20201/29/20201/29/2020 1:37:03 PMPPASS
Replacing existing meter and panel with new meter and sub panels. Phone #: ###-#### Inspection requested via web by Tom Jenkins p/s o/h rec ok
ELE20-00342 Electrical Rough-In1/28/20201/29/20201/29/2020 11:19:23 AMAPASS
wall cover inspection Phone #: ###-#### Inspection requested via web by Ryan Wake Wall rough in ok cover
ELE19-04616 Electrical Rough-In1/28/20201/29/20201/29/2020 11:00:02 AMAPASS
*Inspection for Floor heat* Phone #: ###-#### Inspection requested via web by David Nelson
Master bath floor heat cold splice was partially in wall and wireman moved to where totally in floor at time of inspection. Rough in ok cover
ELE20-00317 Rough-In Permanent Service1/27/20201/29/20201/29/2020 10:33:39 AMAPASS
please call with and corrections. Phone #: ###-#### Inspection requested via web by Brian Hughes
General contractor to provide fire cover for outdoor recessed can in front entrance.
Rough in ok cover p/s u/g n ok
ELE20-00159 Electrical Rough-In1/28/20201/29/20201/29/2020 9:46:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Emmet Bushman
Confirm grounds and neutrals seperated in this sub panel. Bathroom walls and hardlids rough in ok cover
ELE20-00312 Electrical Rough-In1/28/20201/29/20201/29/2020 9:37:15 AMAPASS
Caleb Burke on site contact
ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
Lighting retro in existing grid rough in ok cover.