ELE20-00014
| Rough-In Permanent Service | 1/29/2020 | 1/29/2020 | 1/29/2020 3:44:07 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dean Gernaat House only rough in ok cover p/s u/g n ok
|
ELE20-00014
| Electrical Rough-In | 1/29/2020 | 1/29/2020 | 1/29/2020 3:43:57 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Dean Gernaat Shop not included in description of building permit. 250.32- Seperate buildings or structure fed by feeders or branch circuits shall have a grounding electrode conductor installed. Concrete encased electrode present with no connection to sub-fed panel. No access to upstairs of shop. Feeders to shop not in at time of inspection. Sub-feed in crawl space of house under stairs.
|
ELE19-04522
| Final | 1/28/2020 | 1/29/2020 | 1/29/2020 2:45:32 PM | P | FAIL |
|
|
It Will Be Ready And Open For Ya Thanks Phone #: ###-#### Inspection requested via web by jason shifflett 406.4(D)(3)- Ground fault circuit interupter protected receptacles shall be provided where replacements are made at receptacle outlets that are required to be so protected elsewhere by code. Garage areas. 406.5(D)- Face plates required for receptacle outlets. Master vanity double duplex.
|
ELE19-04755
| Permanent Service | 1/29/2020 | 1/29/2020 | 1/29/2020 1:37:03 PM | P | PASS |
|
|
Replacing existing meter and panel with new meter and sub panels. Phone #: ###-#### Inspection requested via web by Tom Jenkins p/s o/h rec ok
|
ELE20-00342
| Electrical Rough-In | 1/28/2020 | 1/29/2020 | 1/29/2020 11:19:23 AM | A | PASS |
|
|
wall cover inspection Phone #: ###-#### Inspection requested via web by Ryan Wake Wall rough in ok cover
|
ELE19-04616
| Electrical Rough-In | 1/28/2020 | 1/29/2020 | 1/29/2020 11:00:02 AM | A | PASS |
|
|
*Inspection for Floor heat* Phone #: ###-#### Inspection requested via web by David Nelson Master bath floor heat cold splice was partially in wall and wireman moved to where totally in floor at time of inspection. Rough in ok cover
|
ELE20-00317
| Rough-In Permanent Service | 1/27/2020 | 1/29/2020 | 1/29/2020 10:33:39 AM | A | PASS |
|
|
please call with and corrections. Phone #: ###-#### Inspection requested via web by Brian Hughes General contractor to provide fire cover for outdoor recessed can in front entrance. Rough in ok cover p/s u/g n ok
|
ELE20-00159
| Electrical Rough-In | 1/28/2020 | 1/29/2020 | 1/29/2020 9:46:53 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman Confirm grounds and neutrals seperated in this sub panel. Bathroom walls and hardlids rough in ok cover
|
ELE20-00312
| Electrical Rough-In | 1/28/2020 | 1/29/2020 | 1/29/2020 9:37:15 AM | A | PASS |
|
|
Caleb Burke on site contact ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Lighting retro in existing grid rough in ok cover.
|