Inspections for the day of: Tuesday, October 1, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03117 Electrical Rough-In10/1/201910/1/201910/1/2019 3:33:51 PMPPART
Partial rough in Phone #: ###-#### Inspection requested via web by Dave Brueggemann
BCC 4-05-23- Warned of 1 siding with drywall prior to electrical inspection. Ordinance states it shall be unlawful to cover wiring or equipment in anyway with out first having same inspected by electrical inspector. Most 1 sided, front bar shall not be covered in anyway prior to inspection.
Studios and bathrooms wall and hardlids rough in ok cover.
ELE19-03125 Electrical Rough-In9/30/201910/1/201910/1/2019 1:59:43 PMPPASS
John Phone #: ###-####
Bathrooms walls and hardlids rough in ok cover.
ELE18-04501 Final10/1/201910/1/201910/1/2019 1:20:56 PMPFAIL
code for front door 1987 Phone #: ###-#### Inspection requested via web by Dan Rohl
110.3- Entry receptacle on stair wall not hot.
314.16- Boxes shall have adequate cubic space for wiring and device installed. 8 cubic inch box with 11 cubic inches of wiring and device installed. Microwave.
Informed of new policy not to stage house prior to inspection please.
ELE19-03724 Temporary Service10/1/201910/1/201910/1/2019 12:05:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE19-03725 Temporary Service10/1/201910/1/201910/1/2019 11:55:47 AMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE19-03726 Temporary Service10/1/201910/1/201910/1/2019 11:35:43 AMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE19-03693 Electrical Rough-In9/30/201910/1/201910/1/2019 10:57:38 AMAPASS
Under floor raceway and floor box. Dan Hommel Phone #: ###-#### Inspection requested via web by Brad Hoots
Items noted for front office rough in ok cover
ELE18-04645 Final9/30/201910/1/201910/1/2019 10:15:54 AMAFAIL
Geoff Hannaford is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
110.26(D)- Illumination shall be provided for all work spaces about panel boards. Vanilla spaces need illumination for panels.
*ELE18-04645 is attached to BLD18-01882 shell permit. Informed on 12-11-18 that seperate permit needed for other BLD18-03045. No action taken as of 10-1-19. Unable to final until proper permits in place.
ELE19-02034 Final9/30/201910/1/201910/1/2019 9:14:55 AMAPASS
Call 30 minutes in advance if possible. Phone #: ###-#### Inspection requested via web by Steve McCloy
Flex hanging in hallway are the feeds to rooftop units...OK rest of removed and terminated in boxes. Final ok