ELE12-01968
| ELE-Aging Inspection | 10/10/2014 | 10/10/2014 | 10/10/2014 2:08:59 PM | | DONE |
|
|
Waiting on owner
|
ELE12-02026
| ELE-Aging Inspection | 10/10/2014 | 10/10/2014 | 10/10/2014 2:03:42 PM | | DONE |
|
|
Waiting on owner
|
ELE12-02027
| ELE-Aging Inspection | 10/10/2014 | 10/10/2014 | 10/10/2014 2:00:50 PM | | DONE |
|
|
Waiting on owner
|
ELE14-02815
| Rough-In Permanent Service | 10/9/2014 | 10/10/2014 | 10/10/2014 1:42:30 PM | P | PASS |
|
|
Any questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren Rough in ok cover p/s u/g n ok
|
ELE14-02810
| Temporary Service | 10/9/2014 | 10/10/2014 | 10/10/2014 12:48:49 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Lori Stout 400.5(A)- Flexible cord shall be protected by overcurrrent device sized in accordance with table 400.5 (A). #8 cord on 35 amp max. 550.11(D)- JOb trailer shall have feeder sized to electrical installed on trailer. 100 amp min. Nameplate not found. 590.6(B)- Receptical outlets including cord connectors shall have GFCI protection or comply with 590.6(B)(2).
|
ELE14-02679
| Final | 10/9/2014 | 10/10/2014 | 10/10/2014 12:48:45 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dustin Kuester Duplicate request Final ok
|
ELE14-02679
| Final | 10/9/2014 | 10/10/2014 | 10/10/2014 10:24:12 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dustin Kuester Final ok
|
ELE14-02823
| Final | 10/10/2014 | 10/10/2014 | 10/10/2014 9:39:34 AM | A | PASS |
|
|
Unit 2-304. Please call Dave ###-#### for acess Phone #: ###-#### Inspection requested via web by Emmet Bushman Final ok
|
ELE14-02698
| Electrical Rough-In | 10/9/2014 | 10/10/2014 | 10/10/2014 9:14:57 AM | A | PASS |
|
|
underground conduits to sump pumps on tanks for cover Phone #: ###-#### Inspection requested via web by Stan Woodward Rough in ok cover
|
ELE14-02809
| Temporary Service | 10/9/2014 | 10/10/2014 | 10/10/2014 8:55:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins t/s u/g n ok
|
ELE14-02815
| Rough-In Permanent Service | 10/9/2014 | 10/10/2014 | 10/9/2014 3:32:33 PM | A | CANC |
|
|
Any Questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren
|