Inspections for the day of: Friday, October 11, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02434 DOC - Permit Expired10/11/201910/11/201910/11/2019 3:04:35 PMPPASS
Doc expire OK
ELE19-03829 Electrical Rough-In10/10/201910/11/201910/11/2019 2:56:17 PMPPASS
Uffer ground inspection
Contact Shawn Evins
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Concrete encased electrode rough in ok cover
ELE19-02715 Electrical Rough-In10/10/201910/11/201910/11/2019 2:17:45 PMPPASS
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Level 4 phase 2- Kitchenette, records rm, storage rm, and small eastern rm wall rough in ok cover.
ELE19-03464 Permanent Service10/11/201910/11/201910/11/2019 2:16:07 PMPPASS
Installation is exempt from Title 54 Chapter 10 permitting and inspection requirements. Disconnect does not meet NEC 230.70(A)(1). Utility has exclusive control to energize installation. Include any other code violations

250.50- All Grounding electrodes as described in 250.52(A)(1) thru (A)(7) that are present shall be used as grounding electrode system. #6 bare copper conductor run down pole and coiled at bottom of pole is not described in article listed. p/s o/h n ok
ELE19-03741 Final10/11/201910/11/201910/11/2019 1:40:17 PMANH
Contact is Dan Bora Phone #: ###-#### Inspection requested via web by Scott Campbell Called contact to find area work was performed, no answer, left message, in building for 20 minutes no return call. Must recall
ELE19-03929 Rough-In Permanent Service10/10/201910/11/201910/11/2019 11:44:47 AMAFAIL
Thank you :) Phone #: ###-#### Inspection requested via web by Charles Davis
110.3- Family room recessed can junction box cover shall seat tight to box.
210.52(D)- A receptacle outlet shall be installed adjacent to each basin in bathrooms. Master bath has 2 basins.
210.52(E)(3)- Patios or deck accessible form inside house shall have a receptacle outlet installed within its perimeter. Back patio.
300.4- Nail plate above east front garage light.
334.30- Secure NM cable below receptacle in garage near door to house.
OK to foam seal.
ELE19-03302 Conference10/10/201910/11/201910/11/2019 10:00:36 AMADONE
Please call in advance so I can meet you. Phone #: ###-#### Inspection requested via web by Rex Boyles
Discussed mast height and work clearance for replacement of service without disconnecting means for feeds to sub panels. Disconnects woll be in place with new service.
ELE19-03918 Temporary Service10/10/201910/11/201910/11/2019 9:45:08 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
ELE19-02875 Final10/10/201910/11/201910/11/2019 9:10:40 AMAFAIL
access: 4141 Phone #: ###-#### Inspection requested via web by David Nelson
210.8- All GFCi devices shall be located in a readily accessible location. Garage heater receptacle.
422.30- Appliances shall have a disconnecting means. 110.25 lockouts acceptacle. Microwave.