Inspections for the day of: Thursday, October 16, 2014.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01368 ELE-Aging Inspection10/16/201410/16/201410/16/2014 4:21:37 PM DONE
still under construction
MIS14-00210 ELE-Conference10/10/201410/16/201410/16/2014 4:14:03 PMAFAIL
Follow up on progress chuck ###-#### 1st notice 9-16-14, 4-05-18- electrical installation done in past of 10-3 NM cable with out permit. NEC 334.15- NM cable shall be installed with protection from physical damage.
NEC 310.16- Allowable ampacity- #10 ga wire copper 30 amp max. Illegal tap on main lugs of panel, wire protected by main fuses only.
334.6- NM cable shall be install to cables listing. NM cable shall not be installed under trailer " damp location".
Due to no activity 5 working days shall be given to correct issue. Will return on 10-23-14. If still no activity case will be turned over to City Attorney.
ELE14-02369 Final10/16/201410/16/201410/16/2014 3:49:29 PMPPASS
Building is open, call Jimmy for questions. Phone #: ###-#### Inspection requested via web by John Edwards Final ok
ELE14-02877 Final10/15/201410/16/201410/16/2014 2:43:48 PMPPASS
changed out damaged riser wire and grounded meter main Phone #: ###-#### Inspection requested via web by michael hunt Final ok
ELE14-02877 Permanent Service10/16/201410/16/201410/16/2014 2:34:50 PMPPASS
changed out damaged riser wire and grounded meter main Phone #: ###-#### Inspection requested via web by michael hunt p/s o/h rec ok
ELE14-02866 Temporary Service10/16/201410/16/201410/16/2014 2:01:49 PMPPASS
Gate code #1599 Phone #: ###-#### Inspection requested via web by Shaun Kirkman t/s u/g n ok
ELE14-02873 Final10/15/201410/16/201410/16/2014 1:29:39 PMANH
wire ac Phone #: ###-#### Inspection requested via web by PAT MILLER left card
ELE14-02873 Electrical Rough-In10/15/201410/16/201410/16/2014 1:27:51 PMANH
wire ac Phone #: ###-#### Inspection requested via web by PAT MILLER left card
GCE14-00040 GCE-Final10/15/201410/16/201410/16/2014 1:13:05 PMPPASS
(Mandatory Inspection) Signed card Final ok
ELE14-02879 Electrical Rough-In10/15/201410/16/201410/16/2014 10:15:18 AMANH
Inspection requested via web by Terry Scott No contact number provided. Left card
ELE14-02872 Final10/15/201410/16/201410/16/2014 10:00:28 AMAPASS
wire gas furnace Phone #: ###-#### Inspection requested via web by PAT MILLER Final ok
ELE14-02872 Electrical Rough-In10/15/201410/16/201410/16/2014 10:00:08 AMAPASS
wire gas furnace Phone #: ###-#### Inspection requested via web by PAT MILLER Rough in ok cover
ELE14-02881 Electrical Rough-In10/16/201410/16/201410/16/2014 9:33:26 AMAPASS
Phone #: ###-#### Inspection requested via web by Andrea Creek Rough in ok cover
ELE14-02881 Permanent Service10/16/201410/16/201410/16/2014 9:32:58 AMPPASS
Phone #: ###-#### Inspection requested via web by Andrea Creek p/s u/g n ok
ELE14-02478 Electrical Rough-In10/15/201410/16/201410/16/2014 9:11:45 AMAPASS
Underground Electrical Phone #: ###-#### Inspection requested via web by jason williams Interior under slab 105 conduits rjough in ok cover
ELE14-01260 Final10/14/201410/16/201410/16/2014 8:36:10 AMAPASS
I will meet you at project as per our phone call the other day.
early on the 16th.

Thanks

Mike Cole
B ; B Electric
###-#### Phone #: ###-#### Inspection requested via web by Mike Cole Final ok
ELE14-01260 Electrical Rough-In10/16/201410/16/201410/16/2014 8:34:45 AMPPASS
I will meet you at project as per our phone call the other day.
early on the 16th.

Thanks

Mike Cole
B ; B Electric
###-#### Phone #: ###-#### Inspection requested via web by Mike Cole Rough in ok
ELE14-02842 Rough-In Permanent Service10/15/201410/16/201410/15/2014 4:03:34 PMAPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey Rough in ok cover p/s u/g n ok