Inspections for the day of: Thursday, October 17, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03829 Electrical Rough-In10/17/201910/17/201910/17/2019 2:43:26 PMPPASS
Rough-in inspection for the lightning protection ground loop
Contact Shawn Evins
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Lightning arrest ground ring complete west, south, east sides. Still open from crane base to about 20' in from west corner. West side rough in ok cover.
ELE19-03215 Final10/17/201910/17/201910/17/2019 1:51:47 PMPPART
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
210.8(B)- All single phase receptacles up to 50 amp located with in 6' of a sink shall have GFCI protection. Dryer receptacle.
300.11- All cables shall not be supported by grid. Bicycle room LV cables added after ceiling inspection.
330.12- Exposed MC cable installed where subject to physical damage shall be protected from damage. Patches in laundry and S.W. room and reception.
330.30- Support MC in laundry ceiling.
TCO ok for moving in equipment only. Washer and dryer receptacles shall remain accessible.
MIS19-00225 ELE-Final10/17/201910/17/201910/17/2019 1:42:33 PMPPART
Work completed under ELE19-01088. ELE Final ok
ELE19-02169 Final10/17/201910/17/201910/17/2019 1:40:14 PMPCANC
CONTACT: CINDY WOLFE Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
ELE19-03543 Electrical Rough-In10/16/201910/17/201910/17/2019 11:26:02 AMAPASS
Ceiling Rough-in Phone #: ###-#### Inspection requested via web by Kevin Perez
Ceiling rough in ok cover.
ELE19-03679 Final10/14/201910/17/201910/17/2019 10:48:29 AMAPASS
220V Spa Circuit ; Connection , 50A Spa Sub Panel Phone #: ###-#### Inspection requested via web by Louis Keller
Final ok
ELE19-03679 Electrical Rough-In10/17/201910/17/201910/17/2019 10:48:17 AMPPASS
220V Spa Circuit ; Connection , 50A Spa Sub Panel Phone #: ###-#### Inspection requested via web by Louis Keller
All surface mount to pad with slate pavers. Rough in ok
ELE19-03152 Electrical Rough-In10/16/201910/17/201910/17/2019 10:22:13 AMAPASS
Floor heat. Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman
Master bath floor heat rough in ok cover
ELE19-03702 Rough-In Permanent Service10/16/201910/17/201910/17/2019 10:00:54 AMAFAIL
Phone #: ###-#### Inspection requested via web by Heath Thomas
314.25- Recess can junction box covers shall be installed to totally enclose box as per manufacturers instructions. Master hall can, master bed can, kitchen can back junction box covers not flush with box.
* Complete dry sheeting ASAP! It is raining at time of inspection.
ELE19-01340 Final10/16/201910/17/201910/17/2019 9:29:52 AMANH
gc 0588 Phone #: ###-#### Inspection requested via web by Heath Thomas
No access to interior of house. interior garage door locked as well as all other doors. Recall.