GCE13-00116
| GCE-Final | 10/2/2013 | 10/2/2013 | 10/2/2013 3:30:48 PM | P | FAIL |
|
|
Daniel ###-#### call first 210.8 Utility receptical located with in 6' of sink shall be GFCI protected. AC- Manufacturers specs state 25 amp max breaker, 30 amp installed.
|
GCE13-00115
| GCE-Final | 10/2/2013 | 10/2/2013 | 10/2/2013 2:56:22 PM | P | FAIL |
|
|
Daniel ###-#### call first Utility GFCI receptical will not reset
|
GCE13-00114
| GCE-Final | 10/2/2013 | 10/2/2013 | 10/2/2013 2:32:19 PM | P | FAIL |
|
|
Daniel ###-#### call first Garage GFCI receptical miswire, reverse polarity
|
ELE13-02217
| Final | 10/2/2013 | 10/2/2013 | 10/2/2013 1:45:22 PM | A | PASS |
|
|
Chris is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut Final ok
|
ELE13-02716
| Electrical Rough-In | 10/2/2013 | 10/2/2013 | 10/2/2013 12:55:27 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by jody mitchell Service rough in ok
|
ELE13-02716
| Permanent Service | 10/2/2013 | 10/2/2013 | 10/2/2013 12:48:45 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by jody mitchell p/s o/h n ok
|
ELE13-02740
| Permanent Service | 10/2/2013 | 10/2/2013 | 10/2/2013 12:30:25 PM | P | PASS |
|
|
Frank Yantis Phone #: ###-#### p/s u/g n ok
|
ELE13-00418
| Final | 10/2/2013 | 10/2/2013 | 10/2/2013 12:15:28 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Final ok
|
ELE13-01378
| Permanent Service | 10/2/2013 | 10/2/2013 | 10/2/2013 11:12:57 AM | P | PASS |
|
|
Pad 2 p/s u/g n ok
|
ELE13-01377
| Permanent Service | 10/2/2013 | 10/2/2013 | 10/2/2013 11:11:52 AM | P | PASS |
|
|
See ELE13-01376 for R/I inspections Pad 1 p/s u/g n ok
|
ELE13-01378
| Final | 10/2/2013 | 10/2/2013 | 10/2/2013 11:03:43 AM | P | CANC |
|
|
See ELE13-01376 for R/I inspections Wrong request created
|
ELE13-02735
| Permanent Service | 10/1/2013 | 10/2/2013 | 10/2/2013 10:36:34 AM | A | PASS |
|
|
Frank Yantes Phone #: ###-#### p/s u/g n ok
|
ELE13-02734
| Permanent Service | 10/1/2013 | 10/2/2013 | 10/2/2013 10:35:42 AM | A | PASS |
|
|
Frank Yantes Phone #: ###-#### p/s u/g n ok
|
ELE13-02558
| Electrical Rough-In | 10/1/2013 | 10/2/2013 | 10/2/2013 10:08:58 AM | A | PASS |
|
|
Wall cover. Danny on site Phone #: ###-#### >> Inspection requested via web by Buster Bowen Outer office walls for corridor, North, south, and west Interior office wall rough in ok cover
|
ELE13-01848
| Final | 10/1/2013 | 10/2/2013 | 10/2/2013 9:16:09 AM | A | PASS |
|
|
darren Phone #: ###-#### Final ok
|
ELE13-02665
| Final | 10/2/2013 | 10/2/2013 | 10/2/2013 8:46:33 AM | P | PASS |
|
|
Final ok
|
ELE13-02665
| Permanent Service | 10/1/2013 | 10/2/2013 | 10/2/2013 8:45:10 AM | A | PASS |
|
|
There hasn''t been power at this location for over a year now, the recent inspection the inspector was requesting the meterbases to be labeled, they are now labeled and ready for inspection, thanks, TW Phone #: ###-#### >> Inspection requested via web by Stephen Kren p/s u/g rec ok
|