Inspections for the day of: Wednesday, October 2, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03215 Electrical Rough-In10/2/201910/2/201910/2/2019 3:09:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Boarders only for grid in west room only ok cover.
ELE19-03746 Temporary Service10/2/201910/2/201910/2/2019 2:23:36 PMPPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson t/s u/g n ok
ELE19-03747 Temporary Service10/2/201910/2/201910/2/2019 2:22:53 PMPPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson t/s u/g n ok
ELE19-03742 Rough-In Permanent Service10/2/201910/2/201910/2/2019 2:14:18 PMPPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson
Rough in ok cover p/s u/g n ok
ELE19-03740 Rough-In Permanent Service10/2/201910/2/201910/2/2019 2:13:50 PMPFAIL
Phone #: ###-#### Inspection requested via web by Therrin Robertson
210.52(A)(2)- Family room area above 24" tall 8' wide cabinet shall be concidered wall space and shall have receptacles installed. Receptacles shall be located below 5'6".
250.148- Where NM is spliced in a metal box the equipment grounding conductors shall be connected to the box. Pancake boxes.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage. Master bath across from shower. and up front bed. marked with an X.
300.15- NM cable shall terminate in a box. Patio light not stuffed in box.
334.23- Where nm cable is run in attic within 7' of attic access they shall be protected from damage by guard strips. Garage.
ELE18-03961 Final10/2/201910/2/201910/2/2019 1:25:32 PMPPASS
Garage code 1957 Phone #: ###-#### Inspection requested via web by Therrin Robertson Final ok
ELE19-03735 Conference10/1/201910/2/201910/2/2019 1:25:03 PMADONE
GERALD Phone #: ###-####
Unable to talk much due to owner had a conference call shortly after arrival.
Changing wall to living room only and adding an island.
Discussed min receptacle spacing, required to be on small appliance circuit, if micro moves to island dedicated circuit would be needed. Pamphlet given. Owner works as an electrical estimator, seems competent to do work.
Pamphlet given,
ELE19-03315 Final9/29/201910/2/201910/2/2019 12:22:07 PMAPASS
Home owner will be there and I would like to be there for any corrections. Garage code is 1984, just in case. Intersystem bond is installed, I will be in Boise, if you want to call ahead. Thanks! Phone #: ###-#### Inspection requested via web by Shawn Case
Final ok
ELE19-02932 Rough-In Permanent Service10/2/201910/2/201910/2/2019 12:00:58 PMAFAIL
Phone #: ###-#### Inspection requested via web by kevin blackmon
110.3- Recessed can covers shall be completely installed. Master hall back cover not tight to box, up theater looks like penched wire.
300.15- Powder bath fan not hooked up.
334.23- Guard strips shall be in place to protect all wiring within 7' of up stairs attic access.
334.30- Up bed NM shall be secured with in 12" of receptacle box. Saw plumber resting pipe on wiring to measure and cut pipe.
ELE19-03668 Rough-In Permanent Service10/1/201910/2/201910/2/2019 11:15:15 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
See permanent service inspection notes.
ELE19-03668 Electrical Rough-In10/2/201910/2/201910/2/2019 11:15:01 AMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover
ELE19-03668 Permanent Service10/2/201910/2/201910/2/2019 11:14:28 AMPFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.14(D)- Pressure connectors shall be torqued to manufacturers specs. Connection to concrete encased electrode loose.
ELE19-02631 Final10/1/201910/2/201910/2/2019 10:51:21 AMAPASS
garage code 5674 or 9378 Phone #: ###-#### Inspection requested via web by Rodney Monroe Final ok
ELE18-01935 Final10/1/201910/2/201910/2/2019 10:07:02 AMAPART
Final inspection for Unit #406. Contact John (Homey) McElroy. Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Items remaining-
590.6(B)-Temp service has no GFCI protection on 50 amp receptacles, Remove or make compliant.
314.20- All boxes shall have wall cover complete around them to prevent water from entering box or structure.
314.25- All boxes and enclosures shall have covers. Level 3 heat tape panel and level 3 patio switch.
Unit 506 has been permitted seperately.
406 TCO ok
ELE19-00602 Electrical Rough-In10/1/201910/2/201910/2/2019 9:20:21 AMAPASS
4th floor NW Stairwell cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level noted stair walls rough in ok cover