ELE19-04113
| Rough-In Permanent Service | 10/24/2019 | 10/24/2019 | 10/24/2019 3:58:08 PM | P | FAIL |
|
|
Townhome located just west of 5 Mile on the South side of Fairview. Phone #: ###-#### Inspection requested via web by Dan Jennings 240.24- Overcurrent devices shall not be located greater than 6'7" above grade. Bussing located above 6'7". 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. NM cable shall be secured in place at least 1 1/4" from framing surface.
|
ELE19-03027
| Electrical Rough-In | 10/24/2019 | 10/24/2019 | 10/24/2019 3:11:18 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Demizing wall rough in ok cover
|
ELE19-02715
| Electrical Rough-In | 10/23/2019 | 10/24/2019 | 10/24/2019 2:33:40 PM | P | PART |
|
|
Ceiling Inspection, Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Open office area grid rough in ok cover.
|
ELE19-03174
| Electrical Rough-In | 10/23/2019 | 10/24/2019 | 10/24/2019 1:59:32 PM | P | PART |
|
|
Inspect grid ceilings for cover. Mike Hastings ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud 400.12- Flexible cords shall not be installed above ceiling grid. Remove extension cords for emp lighting. Grid boarders only rough in ok
|
ELE19-04089
| Electrical Rough-In | 10/24/2019 | 10/24/2019 | 10/24/2019 1:25:05 PM | P | PASS |
|
|
Trench inspection for hot tub Phone #: ###-#### Inspection requested via web by Bonnie Page Underground all under pavers and stone, rough in ok cover
|
ELE19-03130
| Final | 10/23/2019 | 10/24/2019 | 10/24/2019 12:52:20 PM | A | FAIL |
|
|
There will people there. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan A 200 amp disconnect has been installed to replace a 100 amp disconnect. Change out was completed after hours and reconnected by electrical contractor. 215.2- Feeders shall be sized as per load calculation in parts III, IV, V of artical 220. As per engineer drawing feeders shall be sized to carry 786 amps. 600 KCMIL aluminum installed rated at 340 amps. Feeder in question feeds 2 150amp disconnects and the 200 amp disconnect. Additional 100 amp taps out of main disconnecting means. 250.24(A)(5)- The grounded conductor shall not be connected to non-current carrying metal parts on load side of service disconnecting means. 408-4- Circuit directory shall be complete.
|
ELE19-04012
| Rough-In Permanent Service | 10/23/2019 | 10/24/2019 | 10/24/2019 11:21:58 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Rough in ok cover p/s u/g n ok
|
ELE19-03066
| Final | 10/23/2019 | 10/24/2019 | 10/24/2019 10:45:39 AM | A | FAIL |
|
|
Garage code is 4141. Phone #: ###-#### Inspection requested via web by Dylan Pierce 110.3- Front and rear outdoor receptacles not working. Cold. 210.52(C)- Counter top located in pantry shall have receptacle outlets installed so that no point measured along wall line is more than 24" from a receptacle outlet. 348.30- Furnace flex shall be secure with in 12" of termination. 352.30- PVC service riser shall be secured with in 3' of meter base. 440.6- AC ampacity shall not exceed value on nameplate. 25 amp max, 30 amp installed.
|
ELE19-03224
| Final | 10/23/2019 | 10/24/2019 | 10/24/2019 8:44:45 AM | A | PASS |
|
|
garage code 3484 Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok
|