Inspections for the day of: Thursday, October 24, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04113 Rough-In Permanent Service10/24/201910/24/201910/24/2019 3:58:08 PMPFAIL
Townhome located just west of 5 Mile on the South side of Fairview. Phone #: ###-#### Inspection requested via web by Dan Jennings 240.24- Overcurrent devices shall not be located greater than 6'7" above grade. Bussing located above 6'7".
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates.
NM cable shall be secured in place at least 1 1/4" from framing surface.
ELE19-03027 Electrical Rough-In10/24/201910/24/201910/24/2019 3:11:18 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Demizing wall rough in ok cover
ELE19-02715 Electrical Rough-In10/23/201910/24/201910/24/2019 2:33:40 PMPPART
Ceiling Inspection, Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Open office area grid rough in ok cover.
ELE19-03174 Electrical Rough-In10/23/201910/24/201910/24/2019 1:59:32 PMPPART
Inspect grid ceilings for cover. Mike Hastings ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud 400.12- Flexible cords shall not be installed above ceiling grid. Remove extension cords for emp lighting.
Grid boarders only rough in ok
ELE19-04089 Electrical Rough-In10/24/201910/24/201910/24/2019 1:25:05 PMPPASS
Trench inspection for hot tub Phone #: ###-#### Inspection requested via web by Bonnie Page
Underground all under pavers and stone, rough in ok cover
ELE19-03130 Final10/23/201910/24/201910/24/2019 12:52:20 PMAFAIL
There will people there. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan A 200 amp disconnect has been installed to replace a 100 amp disconnect. Change out was completed after hours and reconnected by electrical contractor.
215.2- Feeders shall be sized as per load calculation in parts III, IV, V of artical 220. As per engineer drawing feeders shall be sized to carry 786 amps. 600 KCMIL aluminum installed rated at 340 amps. Feeder in question feeds 2 150amp disconnects and the 200 amp disconnect. Additional 100 amp taps out of main disconnecting means.

250.24(A)(5)- The grounded conductor shall not be connected to non-current carrying metal parts on load side of service disconnecting means.
408-4- Circuit directory shall be complete.
ELE19-04012 Rough-In Permanent Service10/23/201910/24/201910/24/2019 11:21:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt
Rough in ok cover p/s u/g n ok
ELE19-03066 Final10/23/201910/24/201910/24/2019 10:45:39 AMAFAIL
Garage code is 4141. Phone #: ###-#### Inspection requested via web by Dylan Pierce
110.3- Front and rear outdoor receptacles not working. Cold.
210.52(C)- Counter top located in pantry shall have receptacle outlets installed so that no point measured along wall line is more than 24" from a receptacle outlet.
348.30- Furnace flex shall be secure with in 12" of termination.
352.30- PVC service riser shall be secured with in 3' of meter base.
440.6- AC ampacity shall not exceed value on nameplate. 25 amp max, 30 amp installed.
ELE19-03224 Final10/23/201910/24/201910/24/2019 8:44:45 AMAPASS
garage code 3484 Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok