Inspections for the day of: Tuesday, October 29, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03803 Electrical Rough-In10/29/201910/29/201910/29/2019 2:18:36 PMPPASS
Rough in for new service line, meter, panel, and 2 branch circuits. Phone #: ###-#### Inspection requested via web by Nick Stobbe
Garage may not have wall cover at time of final but owner installed MC cable throughout, any cloth NM cable in place has been abandoned. Rough in ok cover.
ELE19-03803 Permanent Service10/29/201910/29/201910/29/2019 2:02:29 PMPPASS
Rough in for new service line, meter, panel, and 2 branch circuits. Phone #: ###-#### Inspection requested via web by Nick Stobbe
p/s o/h n ok
ELE19-02293 Final10/28/201910/29/201910/29/2019 1:22:07 PMAPASS
garage code 1234, thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE19-01226 Electrical Rough-In10/29/201910/29/201910/29/2019 10:53:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Garrett Collins
Discussed area to right of ranges may have counter top added beyond where receptacle outlets have been roughed in. At final receptacle outlets shall be installed to comply with 210.52(C), would be OK to install at end of cabinet due to pocket door.
Unit 6 rough in ok cover
ELE19-04158 Electrical Rough-In10/29/201910/29/201910/29/2019 10:21:08 AMAPASS
Please inspect under ground conduit for cover. 1” between garage and house Phone #: ###-#### Inspection requested via web by Robert Schroder
Underground noted rough in ok cover
ELE19-02715 Electrical Rough-In10/28/201910/29/201910/29/2019 9:57:00 AMAPASS
rough-in restrooms, Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Area noted rough in ok cover
ELE19-03295 Final10/28/201910/29/201910/29/2019 9:27:24 AMAPASS
Contact lance with questions
208.703.2035 Phone #: ###-#### Inspection requested via web by David Feller Final ok
ELE19-02208 Permanent Service10/28/201910/29/201910/28/2019 3:49:15 PMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI
2 grounding electrode conductors leave panel but wireman could not verify where. Asked to supplement with an additional ground rod as per 250.53 prior to power swing. Will verify on final. p/s o/h n ok