Inspections for the day of: Monday, October 7, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03803 Conference10/7/201910/7/201910/7/2019 4:30:59 PMPDONE
Phone #: ###-#### Inspection requested via web by Nick Stobbe
Discussed service for and wiring in existing detached garage. Minimum receptacles and luminaires required. GFCI protection, WR, TR, secure and support of MC and NM cable. Minimum wire size for 200 amp back to back, grounding electrodes and distance between ground rods. Pamphlet given. Owner has good understanding of scope of work.
ELE19-02467 Final10/7/201910/7/201910/7/2019 4:18:19 PMPFAIL
Cal Phone #: ###-####
110.3- Faceless GFCI device in laundry will not reset or trip.
314.25- All boxes shall have covers. Basement ceiling.
As per parcel note unable to final until street light repair complete.
All other areas in house checked out ok
ELE19-01226 Electrical Rough-In10/4/201910/7/201910/7/2019 3:31:15 PMPPASS
On site Phone #: ###-#### Inspection requested via web by Garrett Collins
BLD states only remodelling kitchens and bathrooms in each unit with smokes added. Wall cover not removed in most of units.
Basement lids and unit 3 only rough in ok cover
ELE19-00602 Electrical Rough-In10/3/201910/7/201910/7/2019 2:44:57 PMPPASS
4th floor PT deck pour. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 4 ramp and around east side pour rough in ok cover
ELE19-03496 Temporary Service10/4/201910/7/201910/7/2019 1:59:36 PMPFAIL
Contact electrical on-site Shawn Evins.
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek
230.95(C)- Ground fault performance test shall be performed on all service disconnecting means rated 150 or more volts to ground and 1000 amps for greater.
Informed must have a core and shell permit, when temp power passes that permit automaticly finals out.
ELE19-03496 Electrical Rough-In10/7/201910/7/201910/7/2019 1:50:34 PMPPASS
Contact electrical on-site Shawn Evins.
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Ground ring and lightning arrest welds rough in ok cover
ELE18-01935 Final10/4/201910/7/201910/7/2019 10:20:21 AMAPASS
Out side electric boxes/ temp power removed
Contact John (Homey) McElroy
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
ELE19-00339 Final10/7/201910/7/201910/7/2019 10:19:56 AMPPASS
Called office number at ###-#### and received verbal permission to final electrical permit for elevator. Final ok
ELE19-00339 Electrical Rough-In10/7/201910/7/201910/7/2019 10:17:29 AMPPASS
Checked on misc dates work performed. Rough in ok
ELE19-03678 Electrical Rough-In10/3/201910/7/201910/7/2019 9:23:51 AMACANC
I wasn''t sure what "type" of inspection I needed. I am starting to wire up my workshop and saw the pre-construction meeting is mandatory. That is what I am trying to schedule. Phone #: ###-#### Inspection requested via web by Curtis Hoovestol
Needed conference.
ELE19-03678 Conference10/7/201910/7/201910/7/2019 9:23:33 AMPDONE
I wasn''t sure what "type" of inspection I needed. I am starting to wire up my workshop and saw the pre-construction meeting is mandatory. That is what I am trying to schedule. Phone #: ###-#### Inspection requested via web by Curtis Hoovestol
Pamphlet given, discussed wall cover required for all wiring below 8', 6" of useable wire at each box prior to termination, type of receptacles, tamper, WR, GFCI protection, inspections required. Owner has done work in past and has good grasp on scope of work.
ELE19-03727 Final10/3/201910/7/201910/7/2019 8:56:23 AMAPASS
Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
All rough in notes on permit ELE18-04645. Final ok
ELE18-04645 Final10/3/201910/7/201910/7/2019 8:55:23 AMAPASS
Geoff Hannaford is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
Final ok