ELE19-03803
| Conference | 10/7/2019 | 10/7/2019 | 10/7/2019 4:30:59 PM | P | DONE |
|
|
Phone #: ###-#### Inspection requested via web by Nick Stobbe Discussed service for and wiring in existing detached garage. Minimum receptacles and luminaires required. GFCI protection, WR, TR, secure and support of MC and NM cable. Minimum wire size for 200 amp back to back, grounding electrodes and distance between ground rods. Pamphlet given. Owner has good understanding of scope of work.
|
ELE19-02467
| Final | 10/7/2019 | 10/7/2019 | 10/7/2019 4:18:19 PM | P | FAIL |
|
|
Cal Phone #: ###-#### 110.3- Faceless GFCI device in laundry will not reset or trip. 314.25- All boxes shall have covers. Basement ceiling. As per parcel note unable to final until street light repair complete. All other areas in house checked out ok
|
ELE19-01226
| Electrical Rough-In | 10/4/2019 | 10/7/2019 | 10/7/2019 3:31:15 PM | P | PASS |
|
|
On site Phone #: ###-#### Inspection requested via web by Garrett Collins BLD states only remodelling kitchens and bathrooms in each unit with smokes added. Wall cover not removed in most of units. Basement lids and unit 3 only rough in ok cover
|
ELE19-00602
| Electrical Rough-In | 10/3/2019 | 10/7/2019 | 10/7/2019 2:44:57 PM | P | PASS |
|
|
4th floor PT deck pour. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Level 4 ramp and around east side pour rough in ok cover
|
ELE19-03496
| Temporary Service | 10/4/2019 | 10/7/2019 | 10/7/2019 1:59:36 PM | P | FAIL |
|
|
Contact electrical on-site Shawn Evins. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek 230.95(C)- Ground fault performance test shall be performed on all service disconnecting means rated 150 or more volts to ground and 1000 amps for greater. Informed must have a core and shell permit, when temp power passes that permit automaticly finals out.
|
ELE19-03496
| Electrical Rough-In | 10/7/2019 | 10/7/2019 | 10/7/2019 1:50:34 PM | P | PASS |
|
|
Contact electrical on-site Shawn Evins. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Ground ring and lightning arrest welds rough in ok cover
|
ELE18-01935
| Final | 10/4/2019 | 10/7/2019 | 10/7/2019 10:20:21 AM | A | PASS |
|
|
Out side electric boxes/ temp power removed Contact John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
|
ELE19-00339
| Final | 10/7/2019 | 10/7/2019 | 10/7/2019 10:19:56 AM | P | PASS |
|
|
Called office number at ###-#### and received verbal permission to final electrical permit for elevator. Final ok
|
ELE19-00339
| Electrical Rough-In | 10/7/2019 | 10/7/2019 | 10/7/2019 10:17:29 AM | P | PASS |
|
|
Checked on misc dates work performed. Rough in ok
|
ELE19-03678
| Electrical Rough-In | 10/3/2019 | 10/7/2019 | 10/7/2019 9:23:51 AM | A | CANC |
|
|
I wasn''t sure what "type" of inspection I needed. I am starting to wire up my workshop and saw the pre-construction meeting is mandatory. That is what I am trying to schedule. Phone #: ###-#### Inspection requested via web by Curtis Hoovestol Needed conference.
|
ELE19-03678
| Conference | 10/7/2019 | 10/7/2019 | 10/7/2019 9:23:33 AM | P | DONE |
|
|
I wasn''t sure what "type" of inspection I needed. I am starting to wire up my workshop and saw the pre-construction meeting is mandatory. That is what I am trying to schedule. Phone #: ###-#### Inspection requested via web by Curtis Hoovestol Pamphlet given, discussed wall cover required for all wiring below 8', 6" of useable wire at each box prior to termination, type of receptacles, tamper, WR, GFCI protection, inspections required. Owner has done work in past and has good grasp on scope of work.
|
ELE19-03727
| Final | 10/3/2019 | 10/7/2019 | 10/7/2019 8:56:23 AM | A | PASS |
|
|
Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce All rough in notes on permit ELE18-04645. Final ok
|
ELE18-04645
| Final | 10/3/2019 | 10/7/2019 | 10/7/2019 8:55:23 AM | A | PASS |
|
|
Geoff Hannaford is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Final ok
|