Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03357 Final11/22/201911/22/201911/22/2019 2:14:36 PMPPASS
Phone #: ###-#### Inspection requested via web by jamie berg
Name plate missing on exterior of mobile home. Assume rating is in manufacturers instructions as per 550.11(D) exception. Chassis bond in place. Final ok
ELE19-03356 Final11/22/201911/22/201911/22/2019 2:07:02 PMPPASS
Phone #: ###-#### Inspection requested via web by jamie berg
Unable to locate name plate on mobile home. Assume rating is in manufacturers instructions in compliance with 550.11(D) exception. Chasis bond in place. Final ok
ELE19-04541 Final11/22/201911/22/201911/22/2019 1:31:44 PMPPASS
Phone #: ###-#### Inspection requested via web by Greg Idsinga
Led lighting retro, occ sensors, emergency lighting complete. Final ok
ELE19-04542 Final11/22/201911/22/201911/22/2019 1:29:26 PMPPASS
Phone #: ###-#### Inspection requested via web by Greg Idsinga
No interior lighting improvement, No sink in warehouse area where supplies and drains are in place.
Emergency and egress lighting final ok
ELE19-04239 Electrical Rough-In11/21/201911/22/201911/22/2019 12:10:08 PMAPASS
Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Walls and hard lids rough in ok cover
ELE19-04240 Electrical Rough-In11/21/201911/22/201911/22/2019 11:53:20 AMAPASS
Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Walls and hard lids rough in ok cover
ELE19-04394 Rough-In Permanent Service11/21/201911/22/201911/22/2019 11:10:02 AMAFAIL
Phone #: ###-#### Inspection requested via web by danny perrine
110.3- Recessed can covers shall be installed tightly to junction boxes. North garage mud room, north spare bed.
250.64(D)(1)- Grounding electrode conductor shall have an external tap and extend to each service disconnect,
250.148- Metal boxes shall be connected to an equipment grounding conductor.
300.4- Nail plates needed in south garage marked with X.
300.15- NM cables shall terminate in a box. Recess can in utility make up missed.
334.12- NM cables shall not be installed where subject to damage. North garage HRs cut corner due to drywall nailer missing.
ELE19-00601 Electrical Rough-In11/22/201911/22/201911/22/2019 10:03:42 AMAPASS
2nd floor common area cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 2 corridor walls and fire lid rough in ok cover.
ELE19-04124 Electrical Rough-In11/21/201911/22/201911/22/2019 9:20:16 AMAPASS
Ceiling inspection please. Thank you and have a bless weekend!!! Phone #: ###-#### Inspection requested via web by Kyle Lott
Grid rough in ok cover
ELE19-02808 Electrical Rough-In11/21/201911/22/201911/22/2019 9:19:36 AMAPASS
Phone #: ###-#### Inspection requested via web by Mike McCarrel
Discussed receptacle locations in face up positions. As per 406.5(E),(F), and (H)- restrictions for counter top, work areas, and seating areas.
Tasting bar soffits and duct pocket walls rough in ok cover