ELE18-04361
| Electrical Rough-In | 11/27/2018 | 11/27/2018 | 11/27/2018 2:06:16 PM | P | PASS |
|
|
Wall rough-in inspection Phone #: ###-#### Inspection requested via web by Kevin Perez Conference room requires 2 floor receptacles due to 535 square ft. Wall rough in ok cover
|
ELE17-02862
| Final | 11/27/2018 | 11/27/2018 | 11/27/2018 1:03:38 PM | A | NR |
|
|
Units 110 , 111 , 112 , 113 , 114 , 115 and Garage Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty 113, 114, 115 checked ok, 110, 111, 112 no access, a barrier shall be in place in garage for feeders.
|
ELE18-01935
| Electrical Rough-In | 11/27/2018 | 11/27/2018 | 11/27/2018 11:45:54 AM | A | PASS |
|
|
Units 201 , 202 , 203 Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted roof dry sheeted with no noticable water in units. Rough in ok cover
|
ELE18-01935
| Conference | 11/27/2018 | 11/27/2018 | 11/27/2018 11:45:27 AM | P | DONE |
|
|
Units 201 , 202 , 203 Phone #: ###-#### Inspection requested via web by Tom Betty Discussed NEC 210.52 general receptacles- required on back of kitchen bar area where faces rooms noted, living, dining, entry, ect. Discussed NEC 334.12- Uses not permitted for installing NM cable. NM cable shall not be installed in a damp or wet location. If NM cable becomes wet due to weather it shall be removed and replaced. Standing water found on level 2 of west building in several units. Will check often.
|
ELE18-04515
| Electrical Rough-In | 11/26/2018 | 11/27/2018 | 11/27/2018 10:46:33 AM | A | PASS |
|
|
Jeff is the site contact, please give about an hour notice so Jeff can meet you there. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Rack system for track lighting in space to south, re plug and switch with updated lighting in space to north. Track lighting rack rough in ok cover
|
ELE18-03384
| Final | 11/26/2018 | 11/27/2018 | 11/27/2018 9:53:03 AM | A | FAIL |
|
|
Garage Code 4053 Phone #: ###-#### Inspection requested via web by Dean Gernaat 210.8- All 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. 1st nook receptacle to right of kitchen sink. 210.52(C)- Pantry counter work space shall have receptacle outlets located so that no point measured along wall line is more than 24" from a receptacle outlet. 348.30(A)- FMC shall be scured with in 12" of island receptacle box. 404.9(A), 406.6- All garage cover plates shall be installed. 408.4- circuit directory shall be complete. GFCI breaker will not reset. 410.16(A)- LED and incandecent luminaires located in master closet shall have totally enclosed lamps.
|