Inspections for the day of: Tuesday, November 27, 2018.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-04361 Electrical Rough-In11/27/201811/27/201811/27/2018 2:06:16 PMPPASS
Wall rough-in inspection Phone #: ###-#### Inspection requested via web by Kevin Perez
Conference room requires 2 floor receptacles due to 535 square ft.
Wall rough in ok cover
ELE17-02862 Final11/27/201811/27/201811/27/2018 1:03:38 PMANR
Units 110 , 111 , 112 , 113 , 114 , 115 and Garage Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
113, 114, 115 checked ok, 110, 111, 112 no access, a barrier shall be in place in garage for feeders.
ELE18-01935 Electrical Rough-In11/27/201811/27/201811/27/2018 11:45:54 AMAPASS
Units 201 , 202 , 203 Phone #: ###-#### Inspection requested via web by Tom Betty
Areas noted roof dry sheeted with no noticable water in units. Rough in ok cover
ELE18-01935 Conference11/27/201811/27/201811/27/2018 11:45:27 AMPDONE
Units 201 , 202 , 203 Phone #: ###-#### Inspection requested via web by Tom Betty
Discussed NEC 210.52 general receptacles- required on back of kitchen bar area where faces rooms noted, living, dining, entry, ect.
Discussed NEC 334.12- Uses not permitted for installing NM cable. NM cable shall not be installed in a damp or wet location. If NM cable becomes wet due to weather it shall be removed and replaced. Standing water found on level 2 of west building in several units. Will check often.
ELE18-04515 Electrical Rough-In11/26/201811/27/201811/27/2018 10:46:33 AMAPASS
Jeff is the site contact, please give about an hour notice so Jeff can meet you there. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
Rack system for track lighting in space to south, re plug and switch with updated lighting in space to north. Track lighting rack rough in ok cover
ELE18-03384 Final11/26/201811/27/201811/27/2018 9:53:03 AMAFAIL
Garage Code 4053 Phone #: ###-#### Inspection requested via web by Dean Gernaat 210.8- All 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. 1st nook receptacle to right of kitchen sink.
210.52(C)- Pantry counter work space shall have receptacle outlets located so that no point measured along wall line is more than 24" from a receptacle outlet.
348.30(A)- FMC shall be scured with in 12" of island receptacle box.
404.9(A), 406.6- All garage cover plates shall be installed.
408.4- circuit directory shall be complete. GFCI breaker will not reset.
410.16(A)- LED and incandecent luminaires located in master closet shall have totally enclosed lamps.