Inspections for the day of: Wednesday, November 27, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-02979 ELE-Aging Inspection11/27/201911/27/201911/27/2019 2:22:57 PM FAIL
Waiting on contractor
ELE19-02541 Rough-In Permanent Service11/21/201911/27/201911/27/2019 1:55:08 PMPNR
This is for a Service/rough-in - please contact Jake with any questions at ###-#### Phone #: ###-#### Inspection requested via web by Deb Morton
Due to delays unable to complete work. See rough in and conference.
ELE19-02541 Conference11/27/201911/27/201911/27/2019 1:52:35 PMPPASS
This is for a Service/rough-in - please contact Jake with any questions at ###-#### Phone #: ###-#### Inspection requested via web by Deb Morton
Discussed requirement for service.
230.6- Service entrance conductors shall be considered outside of building.
230.70(A)(1)- Service disconnecting means shall be located outside of building or immediately upon enterance of the service entrance conductors.
250.50- All grounding electodes present at each building or structure shall be bonded together to form the grounding electrode system.
Informed foreman as long as minimum grounding electrodes needed we would grant permenant service however all present will be needed for final.
An exterior or interior immediately on inside service disconnecting means was not on one line drawing of print created questions.
ELE19-02541 Electrical Rough-In11/27/201911/27/201911/27/2019 1:40:15 PMPPASS
This is for a Service/rough-in - please contact Jake with any questions at ###-#### Phone #: ###-#### Inspection requested via web by Deb Morton
Foyer and electrical room walls and hardlids rough in ok cover.
ELE19-04444 Rough-In Permanent Service11/26/201911/27/201911/27/2019 12:36:06 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok
ELE19-03763 Electrical Rough-In11/25/201911/27/201911/27/2019 11:21:58 AMAPASS
Stephen Phone #: ###-####
Kitchen cabinet layout did not change on range, sink, and bar areas. Informed will need extension rings for boxes 1/4" or more from tile surface. Kitchen rough in ok
ELE19-01582 Electrical Rough-In11/26/201911/27/201911/27/2019 10:54:40 AMAPASS
Exterior Walls Rough-in. Please contact Brett Jenkins. Phone #: ###-#### Inspection requested via web by Deb Morton
Interior walls added to exterior request.
Walls only rough in ok cover.
MIS19-00405 ELE-Final11/27/201911/27/201911/27/2019 10:13:28 AMPPASS
Waiting for 1 special order cover plate then will call for an inspection on ELE19-04610.
MIS Final ok
MIS19-00405 ELE-Conference11/27/201911/27/201911/27/2019 10:11:59 AMPPASS
Permit ELE19-04610 has been pulled for kitchen work noted on building permit plan mod.
ELE19-03585 Final11/27/201911/27/201911/27/2019 10:09:36 AMPPART
All exterior safed off, dining room TCO ok
ELE19-03509 Electrical Rough-In11/26/201911/27/201911/27/2019 10:04:21 AMAPASS
Matt Garcia ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Riser room switch wall, south wall pack, up parapet receptacles in walls rough in ok cover