ELE18-03404
| Final | 11/27/2018 | 11/28/2018 | 11/28/2018 2:15:41 PM | P | FAIL |
|
|
Thank you. Phone #: ###-#### Inspection requested via web by CHRIS CARMINE 210.8(B)- All single phase receptacles and 3 phase receptacles 150 volts or less to ground located outdoors shall have GFCI protection. 422.31(B)- Permanently connected appliances rated 300 va or more shall have a disconnecting means located with in 50' and with in sight. 110.25 lock out acceptacle.
|
ELE18-02826
| Final | 11/28/2018 | 11/28/2018 | 11/28/2018 1:37:22 PM | P | FAIL |
|
|
Johnny-10th floor call for key faub Phone #: ###-#### 210.52(C)- Receptacles installed to serve kitchen island counter space shall be located not more than 6" back from edge of overhang.
|
ELE18-01935
| Electrical Rough-In | 11/28/2018 | 11/28/2018 | 11/28/2018 1:37:02 PM | P | PART |
|
|
Discussed amount of water present on upper floors after rain over night. Contractor has recommended not pulling NM cable until dry sheeting done. Garage 1 side rough in ok cover only.
|
ELE18-04439
| Rough-In Permanent Service | 11/26/2018 | 11/28/2018 | 11/28/2018 11:46:29 AM | A | PASS |
|
|
Contact Seth VanWassenhove Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek ok to cover 2 conduits above meter pack and 1 on front of building with material that looks like rain gutter. Cell tower to be installed on roof. Using a spare meter on meter pack. p/s u/g n ok
|
ELE18-03802
| Electrical Rough-In | 11/27/2018 | 11/28/2018 | 11/28/2018 11:10:27 AM | A | PART |
|
|
Randy. Phone #: ###-#### Inspection requested via web by Sean DeLacy 6 north offices only grid rough in ok cover
|
ELE18-01935
| Electrical Rough-In | 11/28/2018 | 11/28/2018 | 11/28/2018 10:44:31 AM | A | NH |
|
|
Parking Garage one side sheet rock Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty No answer from contact. Must recall when available
|
ELE18-04482
| Final | 11/27/2018 | 11/28/2018 | 11/28/2018 10:30:54 AM | A | FAIL |
|
|
There is a padlock on the office container (the one next to the electrical panel) and the key is on the Cableone box to the right of the meter. Phone #: ###-#### Inspection requested via web by Jonathan Poot 225.39- Outdoor branch circuit disconnecting means shall be a minimum ov 60 amp for a detached structure with 3 or more circuits, 230.24(A)- Vertical clearance over flat roof top surfaces shall be a minimum of 8'. 830.44(A)(4)- Vertical clearance for commmunication cables over flat roof top surfaces shall be a minimum of 8'. BCC- A conditional use permit is required for use of storage container in this manner.
|
ELE18-03892
| Permanent Service | 11/27/2018 | 11/28/2018 | 11/28/2018 9:04:31 AM | A | PASS |
|
|
Etta Phone #: ###-#### p/s o/h n ok
|
ELE18-04534
| Electrical Rough-In | 11/27/2018 | 11/28/2018 | 11/28/2018 6:12:19 AM | P | CANC |
|
|
Contact is Mark Morris. Cover inspection. Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Mark M
|