Inspections for the day of: Wednesday, November 28, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03404 Final11/27/201811/28/201811/28/2018 2:15:41 PMPFAIL
Thank you. Phone #: ###-#### Inspection requested via web by CHRIS CARMINE
210.8(B)- All single phase receptacles and 3 phase receptacles 150 volts or less to ground located outdoors shall have GFCI protection.
422.31(B)- Permanently connected appliances rated 300 va or more shall have a disconnecting means located with in 50' and with in sight.
110.25 lock out acceptacle.
ELE18-02826 Final11/28/201811/28/201811/28/2018 1:37:22 PMPFAIL
Johnny-10th floor call for key faub Phone #: ###-####
210.52(C)- Receptacles installed to serve kitchen island counter space shall be located not more than 6" back from edge of overhang.
ELE18-01935 Electrical Rough-In11/28/201811/28/201811/28/2018 1:37:02 PMPPART
Discussed amount of water present on upper floors after rain over night. Contractor has recommended not pulling NM cable until dry sheeting done. Garage 1 side rough in ok cover only.
ELE18-04439 Rough-In Permanent Service11/26/201811/28/201811/28/2018 11:46:29 AMAPASS
Contact Seth VanWassenhove
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
ok to cover 2 conduits above meter pack and 1 on front of building with material that looks like rain gutter. Cell tower to be installed on roof. Using a spare meter on meter pack.
p/s u/g n ok
ELE18-03802 Electrical Rough-In11/27/201811/28/201811/28/2018 11:10:27 AMAPART
Randy. Phone #: ###-#### Inspection requested via web by Sean DeLacy
6 north offices only grid rough in ok cover
ELE18-01935 Electrical Rough-In11/28/201811/28/201811/28/2018 10:44:31 AMANH
Parking Garage one side sheet rock Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
No answer from contact. Must recall when available
ELE18-04482 Final11/27/201811/28/201811/28/2018 10:30:54 AMAFAIL
There is a padlock on the office container (the one next to the electrical panel) and the key is on the Cableone box to the right of the meter. Phone #: ###-#### Inspection requested via web by Jonathan Poot
225.39- Outdoor branch circuit disconnecting means shall be a minimum ov 60 amp for a detached structure with 3 or more circuits,
230.24(A)- Vertical clearance over flat roof top surfaces shall be a minimum of 8'.
830.44(A)(4)- Vertical clearance for commmunication cables over flat roof top surfaces shall be a minimum of 8'.
BCC- A conditional use permit is required for use of storage container in this manner.
ELE18-03892 Permanent Service11/27/201811/28/201811/28/2018 9:04:31 AMAPASS
Etta Phone #: ###-####
p/s o/h n ok
ELE18-04534 Electrical Rough-In11/27/201811/28/201811/28/2018 6:12:19 AMPCANC
Contact is Mark Morris. Cover inspection. Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Mark M