ELE19-03235
| Electrical Rough-In | 12/12/2019 | 12/12/2019 | 12/12/2019 3:02:03 PM | P | PASS |
|
|
Need inspection for rough - in for walls. Please contact Roger at ###-####. Phone #: ###-#### Inspection requested via web by Deb Morton Called and had attached to BLD19-03974. Walls 1 side of drywall installed, offices being used at time of inspection with open boxes. Wall cover rough in ok cover.
|
ELE19-01406
| Final | 12/12/2019 | 12/12/2019 | 12/12/2019 2:14:33 PM | P | PART |
|
|
Final walk 25 more rooms. 5 kitchenettes . 4 electrical rooms Phone #: ###-#### Inspection requested via web by John Mittleider 210.8(B)(2)- All 120 volt to ground single phase receptacles 50 amp or less shall have GFCI protection. Disposals, counter receptacles, ansil receptacles, refrigerators, and ranges. 314.20- Boxes mounted in a combustible wall cover shall be flush or have extension rings installed. A114 Security and data rm. 314.25- All boxes shall have covers. Play rm above grid, cooler bell box. 404.9- House keeping 2 gang switch cover missing. 422.5(A)(2)- Drinking water coolers shall have GFCI protection. 2 needed. No training shall take place in areas with violations. Approved for storage only. As per Daryl Degrange ok to move in furniture.
|
ELE19-04084
| Final | 12/12/2019 | 12/12/2019 | 12/12/2019 11:01:27 AM | A | PASS |
|
|
please call prior to arrival for access Phone #: ###-#### Inspection requested via web by Patrick Paz Final ok
|
ELE19-04476
| Final | 12/10/2019 | 12/12/2019 | 12/12/2019 10:29:57 AM | A | NH |
|
|
Call Mike With questions or concerns. Thanks Phone #: ###-#### Inspection requested via web by Rob Maes No answer at door. Unable to enter a private residence fenced back yard without an owner or rep from the company on site. Recall when some one is available.
|
ELE19-02541
| Permanent Service | 12/11/2019 | 12/12/2019 | 12/12/2019 10:12:48 AM | A | PASS |
|
|
Jake is the contact. Phone #: ###-#### Inspection requested via web by Deb Morton Grounding electrodes in place at time of inspection are building steel and 2 ground rods. 250.50- All grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at building or structure served shall be bonded together to form the grounding electrode system. 250.52(A)(1)- A underground metal water pipe in contact with the earth 10' of more and electrically continuous. 250.68(C)(1)- Connection of a grounding electrode conductor to an interior metal water piping shall be with in 5' of point of entrance. p/s u/g n ok
|
ELE19-02808
| Electrical Rough-In | 12/11/2019 | 12/12/2019 | 12/12/2019 9:32:01 AM | A | PASS |
|
|
Bar-Kitchen wall Phone #: ###-#### Inspection requested via web by Mike McCarrel Kitchen wall added rough in ok cover
|
ELE19-04031
| Final | 12/11/2019 | 12/12/2019 | 12/12/2019 8:42:48 AM | A | PASS |
|
|
CONTACT NAME ROB LAWRENCE Phone #: ###-#### Inspection requested via web by Deb Gooden No card posted. Final ok
|