Inspections for the day of: Thursday, December 12, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03235 Electrical Rough-In12/12/201912/12/201912/12/2019 3:02:03 PMPPASS
Need inspection for rough - in for walls. Please contact Roger at ###-####. Phone #: ###-#### Inspection requested via web by Deb Morton
Called and had attached to BLD19-03974.
Walls 1 side of drywall installed, offices being used at time of inspection with open boxes.
Wall cover rough in ok cover.
ELE19-01406 Final12/12/201912/12/201912/12/2019 2:14:33 PMPPART
Final walk 25 more rooms. 5 kitchenettes . 4 electrical rooms Phone #: ###-#### Inspection requested via web by John Mittleider
210.8(B)(2)- All 120 volt to ground single phase receptacles 50 amp or less shall have GFCI protection. Disposals, counter receptacles, ansil receptacles, refrigerators, and ranges.
314.20- Boxes mounted in a combustible wall cover shall be flush or have extension rings installed. A114 Security and data rm.
314.25- All boxes shall have covers. Play rm above grid, cooler bell box.
404.9- House keeping 2 gang switch cover missing.
422.5(A)(2)- Drinking water coolers shall have GFCI protection. 2 needed.
No training shall take place in areas with violations. Approved for storage only.
As per Daryl Degrange ok to move in furniture.
ELE19-04084 Final12/12/201912/12/201912/12/2019 11:01:27 AMAPASS
please call prior to arrival for access Phone #: ###-#### Inspection requested via web by Patrick Paz Final ok
ELE19-04476 Final12/10/201912/12/201912/12/2019 10:29:57 AMANH
Call Mike With questions or concerns. Thanks Phone #: ###-#### Inspection requested via web by Rob Maes
No answer at door. Unable to enter a private residence fenced back yard without an owner or rep from the company on site. Recall when some one is available.
ELE19-02541 Permanent Service12/11/201912/12/201912/12/2019 10:12:48 AMAPASS
Jake is the contact. Phone #: ###-#### Inspection requested via web by Deb Morton
Grounding electrodes in place at time of inspection are building steel and 2 ground rods. 250.50- All grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at building or structure served shall be bonded together to form the grounding electrode system. 250.52(A)(1)- A underground metal water pipe in contact with the earth 10' of more and electrically continuous.
250.68(C)(1)- Connection of a grounding electrode conductor to an interior metal water piping shall be with in 5' of point of entrance.
p/s u/g n ok
ELE19-02808 Electrical Rough-In12/11/201912/12/201912/12/2019 9:32:01 AMAPASS
Bar-Kitchen wall Phone #: ###-#### Inspection requested via web by Mike McCarrel Kitchen wall added rough in ok cover
ELE19-04031 Final12/11/201912/12/201912/12/2019 8:42:48 AMAPASS
CONTACT NAME ROB LAWRENCE Phone #: ###-#### Inspection requested via web by Deb Gooden
No card posted. Final ok