ELE18-02960
| Final | 12/13/2018 | 12/13/2018 | 12/13/2018 2:23:00 PM | P | FAIL |
|
|
Call Bill for entry info. Phone #: ###-#### Inspection requested via web by Rhonda Yoast 110.3- Dining room receptacles not working. 314.21- Drywall needs repaired around box up in niche. 406.6- All receptacles shall have covers. 1 in garage left side behind doors, 1 up niche drywall repair. * No access to out BBQ area due to out stairs under construction, interior stair treads not secured. Almost fell when stepped on edge.
|
ELE18-04213
| Rough-In Permanent Service | 12/12/2018 | 12/13/2018 | 12/13/2018 11:12:04 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage by nail plates. Above master bath switches. 300.5(H)- Where cable emerges from grade from a underground conduit they shall be prtected from damage by bushings. UF in family and kitchen. 314.25- All boxes shall have covers. Above master utility in shall part of attic. * Unable to locate AC branch circuit located at back of garage.
|
ELE18-04019
| Electrical Rough-In | 12/12/2018 | 12/13/2018 | 12/13/2018 10:12:27 AM | A | PASS |
|
|
Install under canopy signs. All Primary Power by Others. On Site Contact is Travis @ ###-#### Phone #: ###-#### Inspection requested via web by Ken Olsen Listing and disconnecting means confirmed. rough in ok
|
ELE18-04419
| Electrical Rough-In | 12/12/2018 | 12/13/2018 | 12/13/2018 9:46:21 AM | A | PASS |
|
|
Jay Karel Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Listing and disconnecting means located on remote driver confirmed. Rough in ok cover
|
ELE18-04650
| Permanent Service | 12/13/2018 | 12/13/2018 | 12/13/2018 9:40:37 AM | P | PASS |
|
|
p/s u/g n ok
|
ELE18-04419
| Final | 12/13/2018 | 12/13/2018 | 12/13/2018 9:25:52 AM | P | PASS |
|
|
Jay Karel Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Final ok
|
ELE18-04105
| Electrical Rough-In | 12/12/2018 | 12/13/2018 | 12/13/2018 9:12:50 AM | A | FAIL |
|
|
Go thru the office and they can show you where it is. If you have any questions please feel free to contact Andrew ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 300.4- Where MC cable is rn thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. Several locations
|