Inspections for the day of: Wednesday, December 17, 2014.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00382 ELE-Aging Inspection12/17/201412/17/201412/17/2014 3:26:02 PM DONE
Still under construction
ELE14-03457 Electrical Rough-In12/17/201412/17/201412/17/2014 3:10:09 PMPPASS
Need UFER Ground inspection Phone #: ###-#### Inspection requested via web by Alan Lusk Concrete encased electrode rough in ok cover
ELE14-03435 Electrical Rough-In12/17/201412/17/201412/17/2014 2:26:47 PMPPART
Jerry Phone #: ###-#### Existing sub panel at shop feeders enter through individual knock outs and ground has not been established. Contractor to correct sub feed and grounding by final. Solar rough in ok
ELE14-02796 Electrical Rough-In12/17/201412/17/201412/17/2014 1:49:14 PMPPART
Phone #: ###-#### Inspection requested via web by Thomas Jenkins Office and bathroom walls and hard lid rough in ok cover
ELE14-03473 Final12/16/201412/17/201412/17/2014 1:04:07 PMPFAIL
We Are Changing A meter Socket And Extending The Riser For A Future Remodel Should Be Done Around Noon Phone #: ###-#### Inspection requested via web by jason shifflett 240.24(D)- Overcurrent devices shall not be located in the vicinity of easily ignitable materials such as clothes closets.
110.26- Flat platform work space 30" wide and 36" deep shall be in front of meter base.
4-05-32- Code violations not to be retained.
ELE14-03473 Permanent Service12/17/201412/17/201412/17/2014 1:03:57 PMPPASS
We Are Changing A meter Socket And Extending The Riser For A Future Remodel Should Be Done Around Noon Phone #: ###-#### Inspection requested via web by jason shifflett Reconnect on temporary basis due to cold time of year. Refer to final for notes. p/s o/h rec ok
ELE14-03260 Electrical Rough-In12/17/201412/17/201412/17/2014 12:25:34 PMPPASS
Ryan Phone #: ###-#### Underground from sidewalk to ground box at west picnic area rough in ok cover
ELE14-03471 Temporary Service12/16/201412/17/201412/17/2014 11:42:35 AMAFAIL
Phone #: ###-#### Inspection requested via web by JENNY EMEL 110.12(A)- Unused openings shall be closed.
110.27- Live parts shall be guarded against accidental contact. Secure panel cover.
590.6(B)- Recepticals other than 120 volt shall have GFCI protection
ELE14-02431 Electrical Rough-In12/17/201412/17/201412/17/2014 11:08:05 AMPPASS
Wes ###-#### Refer to ele14-01595 for underground portion of job. Grid rough in for office 127 rough in ok cover.
ELE14-01595 Electrical Rough-In12/16/201412/17/201412/17/2014 11:06:54 AMACANC
Contact: Wes Powell... ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden This permit for underground portion of job. Refer to ele14-02431
ELE13-03105 Electrical Rough-In12/16/201412/17/201412/17/2014 10:21:42 AMAPASS
Entry bathroom walls Phone #: ###-#### Inspection requested via web by matt miller Rough in ok cover
ELE14-03420 Electrical Rough-In12/16/201412/17/201412/17/2014 9:37:03 AMAPASS
fire caulking will be complete in the a.m. Phone #: ###-#### Inspection requested via web by Emmet Bushman Rough in ok cover
ELE14-03420 Permanent Service12/17/201412/17/201412/17/2014 9:28:29 AMPPASS
fire caulking will be complete in the a.m. Phone #: ###-#### Inspection requested via web by Emmet Bushman p/s u/g n ok
ELE14-02464 Final12/16/201412/17/201412/17/2014 9:15:01 AMAPASS
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson Final ok
ELE14-02596 Final12/16/201412/17/201412/17/2014 8:55:47 AMAFAIL
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson 110.7- Wiring integrity. Master bath vanity receptical outlet not working. Dead
300.15- Powder bath lighting outlet shall have box and cover.
406.5- Master vanity receptical outlets shall have covers.
410.16- Closet luminaires that can have incandescent lamps installed shall clear shelf by 12" minimum. up bed closets.
440.6- AC max overcurrent device shall not exceed that on name plate. 30 amp installed on 25 amp max.