Inspections for the day of: Wednesday, December 4, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04615 Electrical Rough-In12/4/201912/4/201912/4/2019 3:12:11 PMPPASS
Office ceilings. Phone #: ###-#### Inspection requested via web by Kevin Burke
Spoke with building maintenance who have a electrical contractors license will close up exposed wiring in this corridor area. Some boxes are associated with TI on this permit and will need confirmed they ar closed up. I will check misc areas in corridor for safety issue at that time.
Office hardlids only rough in ok cover
ELE19-03641 Electrical Rough-In12/4/201912/4/201912/4/2019 12:51:39 PMAPASS
please call a 1/2 hour before on site as no one on site during the day and need to meet and get access through building maintenance. Phone #: ###-#### Inspection requested via web by Jim Noll
Walls and bathroom hardlids, poduim deck rough in ok cover
ELE19-04556 Electrical Rough-In12/3/201912/4/201912/4/2019 11:26:55 AMANH
Please call me if you have any questions door lockbox is SON Phone #: ###-#### Inspection requested via web by TRENT Swaim
Unable to locate address, no answer at contact number, left message
ELE19-04557 Electrical Rough-In12/3/201912/4/201912/4/2019 11:19:25 AMAPASS
Mike Anderson if there are any questions Phone #: ###-#### Inspection requested via web by kendall bender
Rough in ik cover
ELE19-04644 Permanent Service12/3/201912/4/201912/4/2019 11:02:27 AMACANC
Phone #: ###-#### Inspection requested via web by John VanZandt
Needed rough in of the grounding electrode system for a detached garage.
ELE19-04557 Electrical Rough-In12/4/201912/4/201912/4/2019 11:02:16 AMPPASS
Mike Anderson if there are any questions Phone #: ###-#### Inspection requested via web by kendall bender
Grounding electrode system rough in ok cover rest rough in ok cover
ELE19-04472 Rough-In Permanent Service12/3/201912/4/201912/4/2019 10:38:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok
ELE19-03341 Final12/4/201912/4/201912/4/2019 9:57:11 AMAFAIL
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
110.3- Devices shall be wired as per instructions. Hall in from garage w-way mis-wire, 1 3-way locks out other.
314.25- all boxes shall have covers. Upper eave christmas receptacle not trimmed, down bed closet light hanging on wire, up floor receptacle cover not secured.