ELE19-04031
| Electrical Rough-In | 12/5/2019 | 12/5/2019 | 12/5/2019 2:41:09 PM | P | PASS |
|
|
Contact: Rob Lawrence ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Print stated no fire walls or protection requred. Grid rough in ok cover
|
ELE19-00602
| Electrical Rough-In | 12/5/2019 | 12/5/2019 | 12/5/2019 2:37:46 PM | P | PASS |
|
|
7th Floor NW stair tower. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Discussed running service entrance conductors assciated with fire pump on interior of building. Shall comply with 230.6. Level 7 area noted rough in ok cover
|
ELE19-04656
| Temporary Service | 12/4/2019 | 12/5/2019 | 12/5/2019 1:34:13 PM | A | PASS |
|
|
Please feel free to contact Jason ###-#### with any questions. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan t/s o/h n ok
|
ELE19-03993
| Electrical Rough-In | 12/4/2019 | 12/5/2019 | 12/5/2019 10:46:09 AM | A | PASS |
|
|
Install 2 wall signs. Requesting 10:00 am inspection. Phone #: ###-#### Inspection requested via web by Ken Olsen Listing confirmed. Rough in ok.
|
ELE19-03541
| Final | 12/4/2019 | 12/5/2019 | 12/5/2019 10:45:17 AM | A | FAIL |
|
|
Please call Luke for final inspection of Boise Centre entry and security remodel. Please give Luke a 15 minute notice so he can meet you on site. Thanks! Phone #: ###-#### Inspection requested via web by Rafael Castillo Work performed checked ok. North central entrance, left column, an extension cord is run up column and into grid ceiling in violation of 400,12- Uses not permitted for flexible cords. BCC 4 05 32- No code violation shall be retained. Once extension cord has been removed recall. final.
|
ELE19-04230
| Final | 12/4/2019 | 12/5/2019 | 12/5/2019 10:41:09 AM | A | NR |
|
|
Phone #: ###-#### Inspection requested via web by Steven Ragan Dividing walls receptacles checked ok, Furniture not set yet, Whips listing confirmed. Will recall when furniture complete.
|
ELE19-04230
| Electrical Rough-In | 12/5/2019 | 12/5/2019 | 12/5/2019 10:39:49 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Steven Ragan Grid rough in ok cover
|
ELE19-04031
| Electrical Rough-In | 12/4/2019 | 12/5/2019 | 12/5/2019 7:27:03 AM | A | CANC |
|
|
Contact: Rob Lawrence. ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
|