Inspections for the day of: Thursday, December 5, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04031 Electrical Rough-In12/5/201912/5/201912/5/2019 2:41:09 PMPPASS
Contact: Rob Lawrence ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
Print stated no fire walls or protection requred.
Grid rough in ok cover
ELE19-00602 Electrical Rough-In12/5/201912/5/201912/5/2019 2:37:46 PMPPASS
7th Floor NW stair tower. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Discussed running service entrance conductors assciated with fire pump on interior of building. Shall comply with 230.6.
Level 7 area noted rough in ok cover
ELE19-04656 Temporary Service12/4/201912/5/201912/5/2019 1:34:13 PMAPASS
Please feel free to contact Jason ###-#### with any questions. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan t/s o/h n ok
ELE19-03993 Electrical Rough-In12/4/201912/5/201912/5/2019 10:46:09 AMAPASS
Install 2 wall signs. Requesting 10:00 am inspection. Phone #: ###-#### Inspection requested via web by Ken Olsen
Listing confirmed. Rough in ok.
ELE19-03541 Final12/4/201912/5/201912/5/2019 10:45:17 AMAFAIL
Please call Luke for final inspection of Boise Centre entry and security remodel. Please give Luke a 15 minute notice so he can meet you on site.
Thanks! Phone #: ###-#### Inspection requested via web by Rafael Castillo
Work performed checked ok.
North central entrance, left column, an extension cord is run up column and into grid ceiling in violation of 400,12- Uses not permitted for flexible cords.
BCC 4 05 32- No code violation shall be retained.
Once extension cord has been removed recall. final.
ELE19-04230 Final12/4/201912/5/201912/5/2019 10:41:09 AMANR
Phone #: ###-#### Inspection requested via web by Steven Ragan
Dividing walls receptacles checked ok, Furniture not set yet, Whips listing confirmed. Will recall when furniture complete.
ELE19-04230 Electrical Rough-In12/5/201912/5/201912/5/2019 10:39:49 AMPPASS
Phone #: ###-#### Inspection requested via web by Steven Ragan
Grid rough in ok cover
ELE19-04031 Electrical Rough-In12/4/201912/5/201912/5/2019 7:27:03 AMACANC
Contact: Rob Lawrence. ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden