Inspections for the day of: Friday, February 15, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02152 ELE-Aging Inspection2/15/20192/15/20192/15/2019 3:59:50 PM PASS
Sent text to contractor, responded stating will follow up.
ELE15-02087 ELE-Aging Inspection2/15/20192/15/20192/15/2019 3:58:52 PM FAIL
Sent text to contact in morning, waited all day for response. No return message.
ELE15-02091 ELE-Aging Inspection2/15/20192/15/20192/15/2019 3:56:13 PM PASS
Texted contractor who went right to job andsent photos of wiring. Violation is no longer a violation due to changes to ordinance.
ELE15-02091 Final2/15/20192/15/20192/15/2019 3:56:04 PMPPASS
Final ok
ELE19-00345 Electrical Rough-In2/14/20192/15/20192/15/2019 3:30:29 PMPPASS
Randy Phone #: ###-#### Inspection requested via web by Sean DeLacy
Levels 2 and 3 bathrooms rough in ok cover
ELE19-00287 Permanent Service2/15/20192/15/20192/15/2019 2:38:26 PMPPASS
Doing a service change call before you come Phone #: ###-#### Inspection requested via web by Neal Rumsey
Grounding electrode tap shall be external with individual grounding electrode conductor to each service disconnecting enclosure.
p/s u/g rec ok
ELE19-00475 Rough-In Permanent Service2/14/20192/15/20192/15/2019 2:05:00 PMPPASS
electrician on site Phone #: ###-#### Inspection requested via web by Dale Johnson
Garage to be refeed only, underground not in at time of inspection to garage. Lineset to removed from under service location. House rewire rough in ok cover p/s o/h rec ok
ELE18-02562 Final2/14/20192/15/20192/15/2019 1:24:24 PMANR
CONTACT: CALEB BURKE Phone #: ###-#### Inspection requested via web by Deb Gooden
Called contact and they stated commissioning reports are not complete on lighting control and energy measurement devices with remote communication yet. Will complete and recall.
ELE19-00558 Electrical Rough-In2/15/20192/15/20192/15/2019 12:56:42 PMPPASS
Phone #: ###-#### Inspection requested via web by Spencer McLean
Underground 2" from vault to in ground junction box rough in ok cover
ELE18-01935 Permanent Service2/15/20192/15/20192/15/2019 12:08:25 PMAPASS
Main service Call John Phone #: ###-#### Inspection requested via web by Tom Betty
House, tenant, and firepump services
p/s u/g n ok
ELE18-03634 Final2/14/20192/15/20192/15/2019 11:19:39 AMAPASS
Inspector was by on 2-14 AM and planned to return about noon. On site Journeyman found an issue and was unsure if he would have it resolved by noon. He asked me to RS for Friday 2-15-19 just in case. Field contact is Dustin at 208.941.1121. Thanks Phone #: ###-#### Inspection requested via web by Paula Gratiot
Low voltage TV planned for shower with power supply in closet tha tis GFCI protected.
Final ok
ELE19-00526 Rough-In Permanent Service2/14/20192/15/20192/15/2019 10:18:40 AMAFAIL
Phone #: ###-#### Inspection requested via web by Charles Davis
250.32(A)- Seperate garage shall have a grounding electrode system and conductor installed.
314.25- Recessed Can junction box covers shall be completely installed as per instructions.
2 mechanical room, 1 kitchen, 1 down front bedroom.
440.6- Furnace shall be fed by minimum circuit notedd on name plate. 20 amp needed 15 amp installed.