ELE15-02152
| ELE-Aging Inspection | 2/15/2019 | 2/15/2019 | 2/15/2019 3:59:50 PM | | PASS |
|
|
Sent text to contractor, responded stating will follow up.
|
ELE15-02087
| ELE-Aging Inspection | 2/15/2019 | 2/15/2019 | 2/15/2019 3:58:52 PM | | FAIL |
|
|
Sent text to contact in morning, waited all day for response. No return message.
|
ELE15-02091
| ELE-Aging Inspection | 2/15/2019 | 2/15/2019 | 2/15/2019 3:56:13 PM | | PASS |
|
|
Texted contractor who went right to job andsent photos of wiring. Violation is no longer a violation due to changes to ordinance.
|
ELE15-02091
| Final | 2/15/2019 | 2/15/2019 | 2/15/2019 3:56:04 PM | P | PASS |
|
|
Final ok
|
ELE19-00345
| Electrical Rough-In | 2/14/2019 | 2/15/2019 | 2/15/2019 3:30:29 PM | P | PASS |
|
|
Randy Phone #: ###-#### Inspection requested via web by Sean DeLacy Levels 2 and 3 bathrooms rough in ok cover
|
ELE19-00287
| Permanent Service | 2/15/2019 | 2/15/2019 | 2/15/2019 2:38:26 PM | P | PASS |
|
|
Doing a service change call before you come Phone #: ###-#### Inspection requested via web by Neal Rumsey Grounding electrode tap shall be external with individual grounding electrode conductor to each service disconnecting enclosure. p/s u/g rec ok
|
ELE19-00475
| Rough-In Permanent Service | 2/14/2019 | 2/15/2019 | 2/15/2019 2:05:00 PM | P | PASS |
|
|
electrician on site Phone #: ###-#### Inspection requested via web by Dale Johnson Garage to be refeed only, underground not in at time of inspection to garage. Lineset to removed from under service location. House rewire rough in ok cover p/s o/h rec ok
|
ELE18-02562
| Final | 2/14/2019 | 2/15/2019 | 2/15/2019 1:24:24 PM | A | NR |
|
|
CONTACT: CALEB BURKE Phone #: ###-#### Inspection requested via web by Deb Gooden Called contact and they stated commissioning reports are not complete on lighting control and energy measurement devices with remote communication yet. Will complete and recall.
|
ELE19-00558
| Electrical Rough-In | 2/15/2019 | 2/15/2019 | 2/15/2019 12:56:42 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Spencer McLean Underground 2" from vault to in ground junction box rough in ok cover
|
ELE18-01935
| Permanent Service | 2/15/2019 | 2/15/2019 | 2/15/2019 12:08:25 PM | A | PASS |
|
|
Main service Call John Phone #: ###-#### Inspection requested via web by Tom Betty House, tenant, and firepump services p/s u/g n ok
|
ELE18-03634
| Final | 2/14/2019 | 2/15/2019 | 2/15/2019 11:19:39 AM | A | PASS |
|
|
Inspector was by on 2-14 AM and planned to return about noon. On site Journeyman found an issue and was unsure if he would have it resolved by noon. He asked me to RS for Friday 2-15-19 just in case. Field contact is Dustin at 208.941.1121. Thanks Phone #: ###-#### Inspection requested via web by Paula Gratiot Low voltage TV planned for shower with power supply in closet tha tis GFCI protected. Final ok
|
ELE19-00526
| Rough-In Permanent Service | 2/14/2019 | 2/15/2019 | 2/15/2019 10:18:40 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Charles Davis 250.32(A)- Seperate garage shall have a grounding electrode system and conductor installed. 314.25- Recessed Can junction box covers shall be completely installed as per instructions. 2 mechanical room, 1 kitchen, 1 down front bedroom. 440.6- Furnace shall be fed by minimum circuit notedd on name plate. 20 amp needed 15 amp installed.
|