ELE19-00612
| Electrical Rough-In | 2/18/2019 | 2/19/2019 | 2/19/2019 4:09:42 PM | P | PART |
|
|
Please call John @###-#### at least a half hour prior to arrival. Inspection for cover for walls - late afternoon if possible Phone #: ###-#### Inspection requested via web by John Edwards BCC 4-05-32- No code violation shall be retained. 110.26- Minimum work space shall be provided for existing service equipment. Grease containers in front of service disconnects. Partial walls north of bar metal studs only rough in ok cover
|
ELE19-00310
| Final | 2/19/2019 | 2/19/2019 | 2/19/2019 3:48:10 PM | P | PASS |
|
|
Hal Davis Phone #: ###-#### Inspection requested via web by Emmet Bushman No card posted. Final ok
|
ELE18-04858
| Final | 2/18/2019 | 2/19/2019 | 2/19/2019 3:17:45 PM | P | FAIL |
|
|
Final Inspection. Phone #: ###-#### Inspection requested via web by David Feller 210.8- Receptacle outlets located with in 6' of a sink shall have GFCI protection. Break room
|
ELE19-00602
| Electrical Rough-In | 2/19/2019 | 2/19/2019 | 2/19/2019 2:39:12 PM | P | PASS |
|
|
Uffer inspection. Danny is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen Concrete encased electode rough in ok cover
|
ELE18-01608
| Electrical Rough-In | 2/18/2019 | 2/19/2019 | 2/19/2019 1:52:39 PM | P | PASS |
|
|
Underground for site and partial rough-in for EO Wilson building Phone #: ###-#### Inspection requested via web by Mike McCarrel Discussed disconnect locations for interior body of water equipment. All shall have work space clearances and dedicated electrical space if a panel board or switch board as per 110.26. North underground and E.O Wilsom building bathroom ceilings rough in ok cover.
|
ELE18-04702
| Electrical Rough-In | 2/18/2019 | 2/19/2019 | 2/19/2019 11:37:35 AM | A | FAIL |
|
|
Lock box is on the back shop door, code 2020. If you have any questions please feel free to contact CJ ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 210.52(A)- No point measured along floor line shall be more than 6' from a receptacle oulet. living room north of entrance. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. * Service calculation needed for addition of hot tub.
|
ELE16-00727
| Final | 2/18/2019 | 2/19/2019 | 2/19/2019 10:41:07 AM | A | PASS |
|
|
Dan is our contact. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
ELE18-03320
| Electrical Rough-In | 2/18/2019 | 2/19/2019 | 2/19/2019 10:18:58 AM | A | PART |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 2 grid except 227 conferene room rough in ok cover
|
ELE18-01935
| Electrical Rough-In | 2/18/2019 | 2/19/2019 | 2/19/2019 9:51:53 AM | A | PASS |
|
|
Units 411 , 412 , 413 , 414 , 415 Call John Phone #: ###-#### Inspection requested via web by Tom Betty Units noted and 407, 409 rough in ok cover
|
ELE19-00106
| Final | 2/18/2019 | 2/19/2019 | 2/19/2019 9:11:46 AM | A | PASS |
|
|
Contact Brian w/questions. Phone #: ###-#### Inspection requested via web by JENNY EMEL No card posted. Final ok
|
ELE18-03320
| Electrical Rough-In | 2/18/2019 | 2/19/2019 | 2/18/2019 8:22:28 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|