Inspections for the day of: Tuesday, February 19, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00612 Electrical Rough-In2/18/20192/19/20192/19/2019 4:09:42 PMPPART
Please call John @###-#### at least a half hour prior to arrival. Inspection for cover for walls - late afternoon if possible Phone #: ###-#### Inspection requested via web by John Edwards
BCC 4-05-32- No code violation shall be retained. 110.26- Minimum work space shall be provided for existing service equipment. Grease containers in front of service disconnects.
Partial walls north of bar metal studs only rough in ok cover
ELE19-00310 Final2/19/20192/19/20192/19/2019 3:48:10 PMPPASS
Hal Davis Phone #: ###-#### Inspection requested via web by Emmet Bushman
No card posted. Final ok
ELE18-04858 Final2/18/20192/19/20192/19/2019 3:17:45 PMPFAIL
Final Inspection. Phone #: ###-#### Inspection requested via web by David Feller
210.8- Receptacle outlets located with in 6' of a sink shall have GFCI protection. Break room
ELE19-00602 Electrical Rough-In2/19/20192/19/20192/19/2019 2:39:12 PMPPASS
Uffer inspection. Danny is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Concrete encased electode rough in ok cover
ELE18-01608 Electrical Rough-In2/18/20192/19/20192/19/2019 1:52:39 PMPPASS
Underground for site and partial rough-in for EO Wilson building Phone #: ###-#### Inspection requested via web by Mike McCarrel
Discussed disconnect locations for interior body of water equipment. All shall have work space clearances and dedicated electrical space if a panel board or switch board as per 110.26.
North underground and E.O Wilsom building bathroom ceilings rough in ok cover.
ELE18-04702 Electrical Rough-In2/18/20192/19/20192/19/2019 11:37:35 AMAFAIL
Lock box is on the back shop door, code 2020. If you have any questions please feel free to contact CJ ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
210.52(A)- No point measured along floor line shall be more than 6' from a receptacle oulet. living room north of entrance.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates.
* Service calculation needed for addition of hot tub.
ELE16-00727 Final2/18/20192/19/20192/19/2019 10:41:07 AMAPASS
Dan is our contact. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
ELE18-03320 Electrical Rough-In2/18/20192/19/20192/19/2019 10:18:58 AMAPART
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Level 2 grid except 227 conferene room rough in ok cover
ELE18-01935 Electrical Rough-In2/18/20192/19/20192/19/2019 9:51:53 AMAPASS
Units 411 , 412 , 413 , 414 , 415 Call John Phone #: ###-#### Inspection requested via web by Tom Betty
Units noted and 407, 409 rough in ok cover
ELE19-00106 Final2/18/20192/19/20192/19/2019 9:11:46 AMAPASS
Contact Brian w/questions. Phone #: ###-#### Inspection requested via web by JENNY EMEL
No card posted. Final ok
ELE18-03320 Electrical Rough-In2/18/20192/19/20192/18/2019 8:22:28 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton