Inspections for the day of: Thursday, February 21, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03711 ELE-Aging Inspection2/21/20192/21/20192/21/2019 2:42:43 PM FAIL
Emailed contractor, explained importance of needing to final permit. Asked to complete corrections and request final inspection.
ELE15-03629 ELE-Aging Inspection2/21/20192/21/20192/21/2019 2:41:09 PM PASS
Spoke with contractor, he explained work performed. I drove by and inspected. Ballards have been removed, Checked receptacles located next to trees.
ELE15-03629 Final2/21/20192/21/20192/21/2019 2:40:36 PMPPASS
Final ok
ELE15-03756 ELE-Aging Inspection2/21/20192/21/20192/21/2019 2:38:24 PM PASS
Sent text to contractor and he responded will check into and schedule Final
ELE17-03629 Final2/20/20192/21/20192/21/2019 2:35:09 PMPPASS
Matt Murrey is contact, just need to final permit. Phone #: ###-#### Inspection requested via web by Debby Pierce
Final ok
ELE15-03564 Final2/21/20192/21/20192/21/2019 1:29:49 PMPPASS
Contact electrician Rafael Castillo if you have questions or want him to meet you there.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Low voltage simplex system, removed old and installed new supply power existing, inspections required electrically due to voltage limit.
Final ok
ELE18-01608 Permanent Service2/20/20192/21/20192/21/2019 12:58:33 PMPPASS
Permanent service for Gorongosa site. if possible, would like inspection around noon Phone #: ###-#### Inspection requested via web by Mike McCarrel p/s u/g n ok
ELE19-00351 Final2/21/20192/21/20192/21/2019 12:17:14 PMAPASS
Phone #: ###-#### Inspection requested via web by Mark M Final ok
ELE19-00611 Rough-In Permanent Service2/20/20192/21/20192/21/2019 11:26:34 AMAFAIL
Phone #: ###-#### Inspection requested via web by Heath Thomas
300.4- nail plates needed on front garage light, above panel, master bath vanity receptacle 45 degree corner.
314.25- Recessed can junction box cover shall be installed flush with box as per instructions. patio, main bath over tub.
314.29- Access shall be provided for fireplace receptacle box.
ELE19-00505 Final2/20/20192/21/20192/21/2019 10:50:21 AMAFAIL
Office or Matt ###-#### Phone #: ###-#### Inspection requested via web by Matthew White
BCC 4-05-32 No code violations shall be retained.
314.25- All boxes shall have covers installed. Only cover installed is island receptacle
ELE19-00480 Final2/20/20192/21/20192/21/2019 10:35:47 AMAPASS
Phone #: ###-#### Inspection requested via web by Thomas wilson Final ok
ELE19-00280 Rough-In Permanent Service2/20/20192/21/20192/21/2019 10:25:04 AMAFAIL
It will be open. If you have any questions please feel free to contact Tony ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
No service present on house.
300.4- Nail plates needed up stairs front bed room under switch.
314.25- Recessed can junction box covers shall be installed as per instructions. kitchen can front and back covers
ELE18-02854 Electrical Rough-In2/20/20192/21/20192/21/2019 9:35:31 AMAPASS
Building H Full building rough-in for cover inspection.
Contact Scott Wilson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rough in ok cover