Inspections for the day of: Monday, February 24, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00602 Conference2/24/20202/24/20202/24/2020 4:22:01 PMPPASS
Pre TCO walk thru-
- Fire pump replacement being installed due to manufacturing issues.
- Must complete panel schedules.
- Level 2 12"x12" junction has low volt cables not rated for other voltages present in box.
- Elevator yet to complete and inspect.
- Damp location rated receptacles and cover thru out parking garage.
- Exposed wiring for signs shall be terminated in boxes with covers.
- Commissioning report required for generator and lighting systems.
- Label all disconnecting means as to each purpose. 2 located level 6 to 7 on stair tower.
- Ticket stations not in as of 2/24/2020 4pm.
- Stairways have not officially been inspected but appear to have all lighting complete.
ELE19-03038 Electrical Rough-In2/24/20202/24/20202/24/2020 2:09:46 PMPPASS
Don Phone #: ###-####
Main bathroom rough in ok cover.
ELE20-00645 Electrical Rough-In2/24/20202/24/20202/24/2020 1:15:15 PMPPASS
CONTACT IS RYAN WEIDERICH Phone #: ###-#### Inspection requested via web by Scott Campbell
City approved set of prints on site.
Copy room walls only rough in ok cover.
ELE19-04502 Electrical Rough-In2/24/20202/24/20202/24/2020 10:08:56 AMAPASS
Underground pipe for fire pump room and live works Phone #: ###-#### Inspection requested via web by Tom Betty
Asked for city approved set of prints, general foreman unable to located. Will verify next trip.
Area noted underslab rough in ok cover.
ELE19-04444 Final2/21/20202/24/20202/24/2020 9:45:52 AMAPASS
Garage code 1974, thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE19-04616 Final2/21/20202/24/20202/24/2020 9:15:41 AMAPASS
access: 2020 Phone #: ###-#### Inspection requested via web by David Nelson Final ok
ELE20-00577 Final2/21/20202/24/20202/24/2020 8:51:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins. Final ok