ELE19-02541
| Final | 1/29/2020 | 2/3/2020 | 2/3/2020 3:25:57 PM | P | PASS |
|
|
Electrical Final. Jake is the contact Phone #: ###-#### Inspection requested via web by Deb Morton Final ok
|
ELE20-00090
| Final | 2/3/2020 | 2/3/2020 | 2/3/2020 2:44:52 PM | P | FAIL |
|
|
Contact: Caleb Burke Phone #: ###-#### Inspection requested via web by Deb Gooden *Address is 802 W. Bannock, need corrected prior to final. 110.14- Unused breaker spaces shall be closed by approved means. 314.25- All boxes shall have covers installed, most removed due to painting. 408.4- Circuit directories shall be present and accurate.
|
ELE19-00601
| Electrical Rough-In | 2/3/2020 | 2/3/2020 | 2/3/2020 1:35:42 PM | P | PASS |
|
|
Soffit Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Exterior soffits level 1 rough in ok cover
|
ELE20-00206
| Electrical Rough-In | 2/3/2020 | 2/3/2020 | 2/3/2020 12:50:15 PM | P | PASS |
|
|
Installed pvc in back yard for garage and main line for idaho power. Phone #: ###-#### Inspection requested via web by David Kubik Underground noted rough in ok cover.
|
ELE19-01936
| Final | 2/3/2020 | 2/3/2020 | 2/3/2020 11:35:47 AM | A | PASS |
|
|
Please call 30 min ahead Phone #: ###-#### Inspection requested via web by William Andrews 410.10(D)- Suspended luminaire removed in restricted area around bath tub. Final ok
|
ELE16-02304
| Final | 2/3/2020 | 2/3/2020 | 2/3/2020 11:34:05 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by William Andrews Final ok
|
ELE20-00382
| Temporary Service | 1/31/2020 | 2/3/2020 | 2/3/2020 11:10:25 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Richard Gratiot t/s o/h n ok
|
ELE19-03702
| Final | 1/31/2020 | 2/3/2020 | 2/3/2020 10:53:22 AM | A | FAIL |
|
|
lockbox 1319 Phone #: ###-#### Inspection requested via web by Heath Thomas 110.3- Poder bath receptacles not working. Master bath floor heat thermostat too close to wall cannot reset GFCI in right side. 314.16- Receptacle installed for kitchen island counter top shall be of sufficient size for conductor allowance installed. 11.25 cubic inches installed in a 8 cubic inch box.
|
ELE20-00386
| Temporary Service | 2/2/2020 | 2/3/2020 | 2/3/2020 9:51:43 AM | A | FAIL |
|
|
New Temporary service to inspect, questions call Chase- ###-#### Phone #: ###-#### Inspection requested via web by Davin Moore 400.5- Cord conductor shall be large enough for covercurrent device supplying cord. 50 amp. 590.6(B)- GFCI protection shall be provided for all receptacles for temp power Twist lock.
|
ELE19-04131
| Electrical Rough-In | 1/31/2020 | 2/3/2020 | 2/3/2020 9:14:02 AM | A | PASS |
|
|
Inspect raceways under slab in dining rooms , restaurant and bar areas. Phone #: ###-#### Inspection requested via web by John Mittleider Areas noted plus private dining under slab rough in ok cover.
|
ELE19-04839
| Electrical Rough-In | 1/31/2020 | 2/3/2020 | 2/3/2020 8:44:01 AM | A | PASS |
|
|
Fritz Phone #: ###-#### Conference room B-20 switches rough in ok cover.
|