Inspections for the day of: Wednesday, February 6, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00361 Final2/5/20192/6/20192/6/2019 2:29:56 PMPPASS
Phone #: ###-#### Inspection requested via web by Matthew White Final ok
ELE19-00335 Conference2/6/20192/6/20192/6/2019 2:29:43 PMPPASS
Discusssed if conduit run from disconnect to transformer is required to stay out of work space associated with disconnecting means. As per 110.26- work space shall be clear from floor to 6 1/2' minimum height and minimum width and depth of space depending on voltage in front of disconnecting means.
ELE18-04570 Electrical Rough-In2/6/20192/6/20192/6/2019 2:06:48 PMPPASS
rough in cover on first 5 units, 102,104, 106, 202, 204 Phone #: ###-#### Inspection requested via web by mike brown
Units noted rough in ok cover
ELE19-00408 Electrical Rough-In2/4/20192/6/20192/6/2019 1:36:04 PMPPASS
Contact: Josh Mangum... underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
Bar underslab rough in ok cover
ELE19-00448 Electrical Rough-In2/6/20192/6/20192/6/2019 11:34:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Jason Wicks
Garage only rough in ok cover
ELE19-00155 Electrical Rough-In2/5/20192/6/20192/6/2019 11:04:32 AMAPASS
Dean Hunsperger is the contact person (electrician). He needs an underground inspection. Thank you Phone #: ###-#### Inspection requested via web by A.M.E. Office
Concrete encased electrode located on exterior of foundation stubbed out of footing on east side under 2" PVC shall be protected from weather and direct contact with earth. Electrical contractor to encase stub and connection in concrete to protect. Interior and 2" exterior underground rough in ok cover
ELE19-00335 Electrical Rough-In2/6/20192/6/20192/6/2019 10:26:20 AMAPASS
The Knitting Factory wall inspection in concert area. Dimitri Gyteas on site contact. Phone #: ###-#### Inspection requested via web by Jim Noll
North and south pathway lights and receptacles wall rough in ok cover
ELE19-00106 Electrical Rough-In2/4/20192/6/20192/6/2019 10:25:21 AMAPASS
Contact Brian Axelson with any questions.
Ceiling Inspection Requested.

Thank you ; have a great day!
Phone #: ###-#### Inspection requested via web by JENNY EMEL
Grid rough in ok cover
ELE19-00165 Final2/5/20192/6/20192/6/2019 9:16:09 AMACANC
Please call prior to arrival for access. Phone #: ###-#### >> Inspection requested via web by Patrick Paz Inspection cancelled from web by: Patrick Paz
ELE19-00361 Final2/5/20192/6/20192/5/2019 5:49:45 PMACANC
inspection you already did and we corrected the exposed wire on other side of house Phone #: ###-#### >> Inspection requested via web by Matthew White Inspection cancelled from web by: Matthew White