Inspections for the day of: Friday, February 8, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01608 Electrical Rough-In2/7/20192/8/20192/8/2019 2:45:24 PMPPASS
Underground inspection Phone #: ###-#### Inspection requested via web by Mike McCarrel
Underground associated with service pad rough in ok cover
ELE19-00489 Temporary Service2/8/20192/8/20192/8/2019 2:14:37 PMPPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Temp power panel fed from existing service on site. Rough in and final of temp power panel ok
ELE19-00001 Electrical Rough-In2/7/20192/8/20192/8/2019 1:53:17 PMPPASS
Contact: Mike Ennis. PM ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
Discussed requirement for show window receptacles and circuits. 2 windows with show receptacles noted on print, 2 window not shown on print. All window sections required to have show window receptacles and are wide enough to need dedicated circuits for each receptacle as per 210.62 and 220.14(G).
Hardlid rough in ok cover
ELE19-00454 Electrical Rough-In2/7/20192/8/20192/8/2019 1:03:25 PMPPASS
New walls rough for cover Phone #: ###-#### Inspection requested via web by David Feller
Wall rough in ok cover
ELE18-01730 Final2/7/20192/8/20192/8/2019 12:03:18 PMAFAIL
Please call Dominic ###-#### to meet you there. If you have any questions please feel free to contact Darren ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
210.8- All 15 and 20 amp 120 volt receptacle outlets located in a garage shall have GFCI protection. Vac.
210.52(C)(5)- Receptacles installed to serve kitchen counter top areas shall be locagted not more than 20" above counter.
314.16- In ADU receptacle located in end of peninsula shall have a box installed with adequate cubic inch capacity for wiring and device.
314.25- All boxes shall have covers. Front entry to right of front door. Closets shall be blanked or have luminaire installed as per 410.16.
BCC 4-05-24- Inspection required for UF underground to feed post light. Date on wire is new and incomplete.
ELE18-01935 Electrical Rough-In2/7/20192/8/20192/8/2019 9:56:28 AMAPASS
Units 306 , 307 , 309 Call John Phone #: ###-#### Inspection requested via web by Tom Betty Need to sign off inspections on print located on each floor. Areas noted rough in ok cover
ELE19-00468 Electrical Rough-In2/6/20192/8/20192/8/2019 9:06:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Winters LLC
Rewire house rough in ok cover