ELE19-02808
| Final | 3/13/2020 | 3/16/2020 | 3/16/2020 3:07:26 PM | P | FAIL |
|
|
Partial Final Phone #: ###-#### Inspection requested via web by Jeremy Cloud 110.22- Main switches powering this space shall be labelled. 300.22- Electrical penetrations shall be sealed. Cooler. 422.31- Hardwired appliances shall have disconnecting means. * Patio egress not operational.
|
ELE19-04799
| Electrical Rough-In | 3/14/2020 | 3/16/2020 | 3/16/2020 1:55:49 PM | P | PASS |
|
|
Elevated concrete deck rough in 3rd floor deck gridline H to gridline A Phone #: ###-#### Inspection requested via web by Jason Parke Area noted pour rough in ok cover.
|
ELE20-00778
| Electrical Rough-In | 3/16/2020 | 3/16/2020 | 3/16/2020 1:08:01 PM | P | PASS |
|
|
Food truck in Albertsons parking lot Phone #: ###-#### Inspection requested via web by Ryan Wilson 250.64(C)- Grounding electrode conductor shall be continuous. Set screw butt-splice located on farside of side walk. Interior of food shack rough in ok cover.
|
ELE20-00792
| Rough-In Permanent Service | 3/13/2020 | 3/16/2020 | 3/16/2020 10:25:13 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|
ELE20-00764
| Rough-In Permanent Service | 3/13/2020 | 3/16/2020 | 3/16/2020 9:48:44 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard Underground to service not in at time of inspection. Rough in ok cover p/s u/g n ok
|
ELE20-00115
| Final | 3/13/2020 | 3/16/2020 | 3/16/2020 9:20:00 AM | A | FAIL |
|
|
Garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk 348.30- Flex shall be secured with in 12" of a box. Disposal. 406.12- All receptacle outlets located in a dwelling unit shall be tamper resistant type. Bonus room
|
ELE20-00049
| Final | 3/13/2020 | 3/16/2020 | 3/16/2020 8:58:43 AM | A | PASS |
|
|
Garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|