Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00875 Rough-In Permanent Service3/18/20193/18/20193/18/2019 2:15:06 PMPFAIL
please move inspection to PM today. Phone #: ###-#### Inspection requested via web by Bob Glenn
250.64(D)(1)- Grounding electrode conductor tap shall extend to the inside of each disconnecting means enclosure. Looping through 1 disconnecting means to another creates future difficulties.
300.4- Nail plates needed in kitchen island.
334.12- NM cable shall not be installed where subject to damage. Garage truss pinch point gang nail may damage NM cable.
ELE18-04827 Final3/18/20193/18/20193/18/2019 1:26:59 PMPPASS
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok
ELE18-02608 Final3/18/20193/18/20193/18/2019 12:51:06 PMPPASS
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok
ELE16-02769 ELE-Aging Inspection3/15/20193/18/20193/18/2019 11:56:51 AMAFAIL
Kyle ###-####
210.12- All new wiring supplying bedroom outlets shall have AFCI protection.
If no action is taken permit will be doc finaled and owner will have to pull and pay for new permit as per Daryl DeGrange Chief Electrical Inspector.
ELE19-00900 Electrical Rough-In3/15/20193/18/20193/18/2019 11:06:47 AMAPASS
Please call Fred Sleight one hour ahead @ ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Bonnie Page
Kitchen and dining area remodel rough in ok cover
ELE19-00696 Final3/15/20193/18/20193/18/2019 10:25:49 AMAFAIL
It will be open. If you have any questions please feel free to contact Clay ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
314.25- All boxes shall have covers. Photo cell and out light not done.
ELE19-00701 Final3/15/20193/18/20193/18/2019 10:25:14 AMAFAIL
It will be open. If you have any questions please feel free to contact Clay ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
314.25- All boxes shall have covers. Photo cell and out light not done.
ELE19-00711 Electrical Rough-In3/15/20193/18/20193/18/2019 9:43:29 AMAPASS
Brian Phone #: ###-####
listing and scope of work rough in ok
ELE18-01391 Electrical Rough-In3/16/20193/18/20193/18/2019 9:03:09 AMANH
level 4 area A hard lid rough in. Phone #: ###-#### Inspection requested via web by Tom Betty
Called contact, no answer, left message.
ELE19-00126 Final3/15/20193/18/20193/18/2019 8:51:34 AMAPASS
Install on e sign over entrance reading Healthy Pet. ALL PRIMARY POWER BY OTHERS. Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
ELE19-00875 Rough-In Permanent Service3/15/20193/18/20193/18/2019 7:34:15 AMACANC
Contact Troy with any question or concerns. ###-####
Thanks! Phone #: ###-#### >> Inspection requested via web by Bob Glenn Inspection cancelled from web by: Bob Glenn