Inspections for the day of: Friday, March 20, 2020.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00892 Final3/20/20203/20/20203/20/2020 2:02:39 PMPNH
Electrical Final. Phone #: ###-#### Inspection requested via web by Deb Morton No access due building closed until virus threat is over. Will recall when accessible.
ELE20-01019 Temporary Service3/20/20203/20/20203/20/2020 12:57:54 PMPPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard t/s u/g n ok
ELE20-00634 Temporary Service3/20/20203/20/20203/20/2020 12:57:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard t/s u/g n ok
ELE20-00762 Temporary Service3/20/20203/20/20203/20/2020 12:57:01 PMPFAIL
Phone #: ###-#### Inspection requested via web by Troy Ballard
250.24(A)(4)- A main bonding jumper shall be installed to connect the grounding electrode conductor to the grounded conductor.
ELE20-00635 Temporary Service3/20/20203/20/20203/20/2020 12:54:45 PMPFAIL
Phone #: ###-#### Inspection requested via web by Troy Ballard
110.12- Electrical equipment shall not be damaged. Rust has complromized lugs and meter base jaws.
250.24(A)(4)- A main bonding jumper shall be installed connecting grounded conductor and the grounding electrode conductor.
ELE20-01009 Rough-In Permanent Service3/19/20203/20/20203/20/2020 11:15:36 AMACANC
Phone #: ###-#### Inspection requested via web by kevin blackmon
Duplicate request
ELE20-01009 Rough-In Permanent Service3/19/20203/20/20203/20/2020 11:15:03 AMAPASS
Phone #: ###-#### Inspection requested via web by kevin blackmon
Rough in ok cover p/s u/g n ok
ELE19-02808 Final3/19/20203/20/20203/20/2020 10:19:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
As per 2015 IECC C408.3.1 a lighting system commissioning report shall be completed by the registered disign professional prior to final.
BCC 4-05-32, No code violation shall be retained. AC disconnecting means for tasting lounge is missing interior cover and has exposed wiring to public and is located next to a gathering shelter on east side of tasting lounge.
ELE20-00988 Electrical Rough-In3/18/20203/20/20203/20/2020 9:26:34 AMAPASS
Contact: Jeremy Thornock.. Uffer inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden

City approved set of prints in General contractors office located at 404 S. 8th St. Suite L138, Verified. Green tag delivered in contractors office.
Concrete encased electrode rough in ok cover.
ELE20-00209 Final3/19/20203/20/20203/20/2020 8:36:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Steven Ragan Final ok
ELE20-00209 Final3/16/20203/20/20203/17/2020 12:38:23 PMACANC
Phone #: ###-#### >> Inspection requested via web by Steven Ragan Inspection cancelled from web by: Steven Ragan