ELE20-00892
| Final | 3/20/2020 | 3/20/2020 | 3/20/2020 2:02:39 PM | P | NH |
|
|
Electrical Final. Phone #: ###-#### Inspection requested via web by Deb Morton No access due building closed until virus threat is over. Will recall when accessible.
|
ELE20-01019
| Temporary Service | 3/20/2020 | 3/20/2020 | 3/20/2020 12:57:54 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard t/s u/g n ok
|
ELE20-00634
| Temporary Service | 3/20/2020 | 3/20/2020 | 3/20/2020 12:57:28 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard t/s u/g n ok
|
ELE20-00762
| Temporary Service | 3/20/2020 | 3/20/2020 | 3/20/2020 12:57:01 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard 250.24(A)(4)- A main bonding jumper shall be installed to connect the grounding electrode conductor to the grounded conductor.
|
ELE20-00635
| Temporary Service | 3/20/2020 | 3/20/2020 | 3/20/2020 12:54:45 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard 110.12- Electrical equipment shall not be damaged. Rust has complromized lugs and meter base jaws. 250.24(A)(4)- A main bonding jumper shall be installed connecting grounded conductor and the grounding electrode conductor.
|
ELE20-01009
| Rough-In Permanent Service | 3/19/2020 | 3/20/2020 | 3/20/2020 11:15:36 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by kevin blackmon Duplicate request
|
ELE20-01009
| Rough-In Permanent Service | 3/19/2020 | 3/20/2020 | 3/20/2020 11:15:03 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kevin blackmon Rough in ok cover p/s u/g n ok
|
ELE19-02808
| Final | 3/19/2020 | 3/20/2020 | 3/20/2020 10:19:28 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud As per 2015 IECC C408.3.1 a lighting system commissioning report shall be completed by the registered disign professional prior to final. BCC 4-05-32, No code violation shall be retained. AC disconnecting means for tasting lounge is missing interior cover and has exposed wiring to public and is located next to a gathering shelter on east side of tasting lounge.
|
ELE20-00988
| Electrical Rough-In | 3/18/2020 | 3/20/2020 | 3/20/2020 9:26:34 AM | A | PASS |
|
|
Contact: Jeremy Thornock.. Uffer inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden City approved set of prints in General contractors office located at 404 S. 8th St. Suite L138, Verified. Green tag delivered in contractors office. Concrete encased electrode rough in ok cover.
|
ELE20-00209
| Final | 3/19/2020 | 3/20/2020 | 3/20/2020 8:36:38 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Steven Ragan Final ok
|
ELE20-00209
| Final | 3/16/2020 | 3/20/2020 | 3/17/2020 12:38:23 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Steven Ragan Inspection cancelled from web by: Steven Ragan
|