ELE19-00335
| Final | 3/5/2019 | 3/5/2019 | 3/5/2019 3:30:07 PM | P | CANC |
|
|
can this please be the last inspection time for the day if possible. thanks Phone #: ###-#### Inspection requested via web by Jim Noll Jim Noll called and asked to cancel inspection and they would recall. Thanks for heads up.
|
ELE19-00127
| Permanent Service | 3/5/2019 | 3/5/2019 | 3/5/2019 3:09:48 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud p/s u/g n ok
|
ELE18-00240
| Final | 3/5/2019 | 3/5/2019 | 3/5/2019 2:46:00 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by David Baker See RI
|
ELE18-00240
| Electrical Rough-In | 3/5/2019 | 3/5/2019 | 3/5/2019 2:17:54 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by David Baker Listing and disconnecing means confirmed. 300.3(A)- Single conductors shall be installed in a wiring method recognized in chapter 3 of NEC. 300.18- Raceways shall be installed in complete runs. Exposed single conductors feeding sign through EMT not terminated at sign, wire leaves conduit and enter unbushed opening.
|
ELE19-00371
| Electrical Rough-In | 3/5/2019 | 3/5/2019 | 3/5/2019 2:13:53 PM | P | PASS |
|
|
Underground inspection please call cody for questions 2084843754q Phone #: ###-#### Inspection requested via web by Shane Lott Underground fron in ground junctin box to a single light pole rough in ok cover.
|
ELE18-00082
| Final | 3/5/2019 | 3/5/2019 | 3/5/2019 1:40:06 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Baker Final ok
|
ELE18-00082
| Electrical Rough-In | 3/5/2019 | 3/5/2019 | 3/5/2019 1:15:46 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Baker Listing and disconnecting means confirmed, rough in ok cover
|
ELE19-00702
| Temporary Service | 3/5/2019 | 3/5/2019 | 3/5/2019 1:14:12 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE19-00703
| Temporary Service | 3/5/2019 | 3/5/2019 | 3/5/2019 12:47:14 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE19-00679
| Final | 3/4/2019 | 3/5/2019 | 3/5/2019 12:13:53 PM | A | NH |
|
|
Inspection for 20 amp ductless split rough-in and final inspection Phone #: ###-#### Inspection requested via web by shane miller No answer at door left card
|
ELE18-04499
| Electrical Rough-In | 3/4/2019 | 3/5/2019 | 3/5/2019 12:01:45 PM | A | PASS |
|
|
Dusty Phone #: ###-#### Corrections complete. bathroom rough in ok cover
|
ELE19-00090
| Final | 3/5/2019 | 3/5/2019 | 3/5/2019 11:39:22 AM | A | PASS |
|
|
Smoke detectors are now AFCI protected. Phone #: ###-#### Inspection requested via web by Dan Hilke Final ok
|
ELE18-04101
| Final | 3/4/2019 | 3/5/2019 | 3/5/2019 11:25:32 AM | A | PASS |
|
|
GARAGE CODE 7573 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE19-00758
| Electrical Rough-In | 3/4/2019 | 3/5/2019 | 3/5/2019 10:34:33 AM | A | PASS |
|
|
Underground and bonding for swimming pool/spa. Underground for: (5) pool lights, (1) spa light, (3) bubbles, (3) sheer descents, (1) autocover motor, (1) autocover key switch Bonding for: (4) EQ corners, (2) autocover, (1) water, (1) steel/equipment, (1) pergola columns Phone #: ###-#### Inspection requested via web by Lars Johnson For areas noted rough in ok cover
|
ELE19-00613
| Final | 3/4/2019 | 3/5/2019 | 3/5/2019 10:08:48 AM | A | FAIL |
|
|
Call Logan with questions. Nobody on site. Everything accessible. Phone #: ###-#### Inspection requested via web by BRS Permitting Still not tight, can turn by hand.
|
ELE19-00596
| Final | 3/4/2019 | 3/5/2019 | 3/5/2019 9:43:33 AM | A | PART |
|
|
Contact: Rick Badley Phone #: ###-#### Inspection requested via web by Deb Gooden Down storage/shop area. tco ok
|
ELE19-00335
| Final | 3/5/2019 | 3/5/2019 | 3/5/2019 9:39:26 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Jim Noll Corrections not all complete. Open boxes up mech., open boxes above stage floor. (Trouble shooting)
|