ELE19-00661
| Final | 4/10/2019 | 4/10/2019 | 4/10/2019 3:26:41 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt 110.3- Devices shall be installed as per manufacturers instructions. Reverse polarity on 4 receptacles, above and each side of fireplace, and back patio GFCI receptacle. * Master shower can not working. * Master stool fan not installed. It is sitting on throne.
|
ELE19-01204
| Final | 4/9/2019 | 4/10/2019 | 4/10/2019 3:07:18 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson 250.32- Seperate buildings or structures fed by feeders or branch circuits shall have a grounding electrode system installed.
|
ELE19-00738
| Final | 4/10/2019 | 4/10/2019 | 4/10/2019 2:24:25 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Future power not connected and is buried in wall. Final ok
|
ELE17-02547
| Final | 4/10/2019 | 4/10/2019 | 4/10/2019 1:58:57 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by chris hopkins Final ok
|
ELE17-02547
| Electrical Rough-In | 4/10/2019 | 4/10/2019 | 4/10/2019 1:24:01 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by chris hopkins Listing confirmed. Rough in ok.
|
ELE18-01642
| Final | 4/10/2019 | 4/10/2019 | 4/10/2019 1:23:01 PM | P | NH |
|
|
Justin Phone #: ###-#### Called 12:58pm, left message, was in area 25 minutes, no longer in area, please reschedule another day.
|
ELE18-01567
| Final | 4/10/2019 | 4/10/2019 | 4/10/2019 1:11:05 PM | P | PASS |
|
|
does not have to be done on this date. Phone #: ###-#### Inspection requested via web by chris hopkins Final ok
|
ELE18-01567
| Electrical Rough-In | 4/10/2019 | 4/10/2019 | 4/10/2019 1:10:39 PM | P | PASS |
|
|
does not have to be done on this date. Phone #: ###-#### Inspection requested via web by chris hopkins Listing confirmed. Rough in ok cover.
|
ELE18-04785
| Electrical Rough-In | 4/9/2019 | 4/10/2019 | 4/10/2019 12:43:08 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins Interior walls rough in ok cover
|
ELE18-01608
| Electrical Rough-In | 4/9/2019 | 4/10/2019 | 4/10/2019 12:12:58 PM | A | PASS |
|
|
Bathroom ceilings for cover Phone #: ###-#### Inspection requested via web by Mike McCarrel Access shall be provided for emergency ballasts. Bathrooms and entrance. Rough in ok cover
|
ELE19-00241
| Electrical Rough-In | 4/9/2019 | 4/10/2019 | 4/10/2019 11:13:00 AM | A | PASS |
|
|
CONTACT NAME IS DAN SCHMIDT. CEILING ROUGH IN PLEASE AND THANK YOU Phone #: ###-#### Inspection requested via web by Deb Gooden Grid complete with some decorative luminaires being installed after grid rough in ok cover
|
ELE18-01935
| Electrical Rough-In | 4/9/2019 | 4/10/2019 | 4/10/2019 10:33:14 AM | A | PASS |
|
|
3RD , 4TH , 5TH floor trash and comm rm. , 3RD Bath rm. and 306 , 307 , 312 drop ceilings Phone #: ###-#### Inspection requested via web by Tom Betty Items noted adding fireplaces in units noted and level 2 planters wall pour in front of units 201, 202, 203 rough in ok cover
|
ELE19-01273
| Temporary Service | 4/9/2019 | 4/10/2019 | 4/10/2019 9:21:04 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE19-00756
| Final | 4/9/2019 | 4/10/2019 | 4/10/2019 9:15:36 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt 300.15- All cables shall terminate in a box. Dishwasher not hooked up. 406.6- All devices shall have covers. Kitchen counter device covers missing. 422.31- All hard wired appliances shall have a disconnecting means. 110.25- lockouts acceptable. Dishwasher
|