Inspections for the day of: Wednesday, April 10, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00661 Final4/10/20194/10/20194/10/2019 3:26:41 PMPFAIL
Phone #: ###-#### Inspection requested via web by Greg Traudt
110.3- Devices shall be installed as per manufacturers instructions. Reverse polarity on 4 receptacles, above and each side of fireplace, and back patio GFCI receptacle.
* Master shower can not working.
* Master stool fan not installed. It is sitting on throne.
ELE19-01204 Final4/9/20194/10/20194/10/2019 3:07:18 PMPFAIL
Phone #: ###-#### Inspection requested via web by Ryan Wilson
250.32- Seperate buildings or structures fed by feeders or branch circuits shall have a grounding electrode system installed.
ELE19-00738 Final4/10/20194/10/20194/10/2019 2:24:25 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender
Future power not connected and is buried in wall. Final ok
ELE17-02547 Final4/10/20194/10/20194/10/2019 1:58:57 PMPPASS
Phone #: ###-#### Inspection requested via web by chris hopkins Final ok
ELE17-02547 Electrical Rough-In4/10/20194/10/20194/10/2019 1:24:01 PMPPASS
Phone #: ###-#### Inspection requested via web by chris hopkins
Listing confirmed. Rough in ok.
ELE18-01642 Final4/10/20194/10/20194/10/2019 1:23:01 PMPNH
Justin Phone #: ###-####
Called 12:58pm, left message, was in area 25 minutes, no longer in area, please reschedule another day.
ELE18-01567 Final4/10/20194/10/20194/10/2019 1:11:05 PMPPASS
does not have to be done on this date. Phone #: ###-#### Inspection requested via web by chris hopkins Final ok
ELE18-01567 Electrical Rough-In4/10/20194/10/20194/10/2019 1:10:39 PMPPASS
does not have to be done on this date. Phone #: ###-#### Inspection requested via web by chris hopkins
Listing confirmed. Rough in ok cover.
ELE18-04785 Electrical Rough-In4/9/20194/10/20194/10/2019 12:43:08 PMAPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Interior walls rough in ok cover
ELE18-01608 Electrical Rough-In4/9/20194/10/20194/10/2019 12:12:58 PMAPASS
Bathroom ceilings for cover Phone #: ###-#### Inspection requested via web by Mike McCarrel
Access shall be provided for emergency ballasts. Bathrooms and entrance. Rough in ok cover
ELE19-00241 Electrical Rough-In4/9/20194/10/20194/10/2019 11:13:00 AMAPASS
CONTACT NAME IS DAN SCHMIDT.
CEILING ROUGH IN PLEASE AND THANK YOU Phone #: ###-#### Inspection requested via web by Deb Gooden
Grid complete with some decorative luminaires being installed after grid rough in ok cover
ELE18-01935 Electrical Rough-In4/9/20194/10/20194/10/2019 10:33:14 AMAPASS
3RD , 4TH , 5TH floor trash and comm rm. , 3RD Bath rm. and 306 , 307 , 312 drop ceilings Phone #: ###-#### Inspection requested via web by Tom Betty
Items noted adding fireplaces in units noted and level 2 planters wall pour in front of units 201, 202, 203 rough in ok cover
ELE19-01273 Temporary Service4/9/20194/10/20194/10/2019 9:21:04 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE19-00756 Final4/9/20194/10/20194/10/2019 9:15:36 AMAFAIL
Phone #: ###-#### Inspection requested via web by Greg Traudt
300.15- All cables shall terminate in a box. Dishwasher not hooked up.
406.6- All devices shall have covers. Kitchen counter device covers missing.
422.31- All hard wired appliances shall have a disconnecting means. 110.25- lockouts acceptable. Dishwasher