ELE19-01226
| Permanent Service | 4/11/2019 | 4/12/2019 | 4/12/2019 2:48:54 PM | P | PASS |
|
|
Ok to energize. Neil on site Phone #: ###-#### Inspection requested via web by Garrett Collins 65k rated main, will verify available fault current in future as per 110.9 and 110.24. p/s o/h rec ok
|
ELE18-02369
| Permanent Service | 4/10/2019 | 4/12/2019 | 4/12/2019 2:12:04 PM | P | CANC |
|
|
Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell Needed rough in inspection.
|
ELE18-02369
| Electrical Rough-In | 4/12/2019 | 4/12/2019 | 4/12/2019 2:11:42 PM | P | PASS |
|
|
Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell Discussed the work depth for HVAC unit on roof disconnecting means at 480 volt. As per 110.26(A)(1) a minimum depth of 3'6" shall be present. Disconnects will have to be moved to another location. Energize sub gear on all floors rough in ok.
|
ELE19-01061
| Electrical Rough-In | 4/11/2019 | 4/12/2019 | 4/12/2019 1:18:08 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Caleb Gaylord Unit A only rough in ok cover
|
ELE19-01141
| Final | 4/11/2019 | 4/12/2019 | 4/12/2019 11:56:21 AM | A | FAIL |
|
|
if access is needed contact homeowner prior to inspection to meet at location @ Ryan ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON 440.6- Overcurrent shall not exceed maximum shown on name plate rating. 25 amp max 30 fuses installed.
|
ELE19-00642
| Final | 4/11/2019 | 4/12/2019 | 4/12/2019 11:19:28 AM | A | PASS |
|
|
Garage code is 1114 Phone #: ###-#### Inspection requested via web by Kevin Heideman Final ok
|
ELE19-00549
| Final | 4/11/2019 | 4/12/2019 | 4/12/2019 10:29:37 AM | A | PASS |
|
|
Final please. Thank you Phone #: ###-#### Inspection requested via web by Kyle Lott Final ok
|
ELE19-00596
| Electrical Rough-In | 4/11/2019 | 4/12/2019 | 4/12/2019 10:28:09 AM | A | PASS |
|
|
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden As per notes on building permit a seperate building permit and electrical permit is required for finish out of dwelling unit. Walls and hardlids of dwelling unit rough in ok cover
|
ELE19-01199
| Rough-In Permanent Service | 4/11/2019 | 4/12/2019 | 4/12/2019 8:55:17 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|