Inspections for the day of: Friday, April 12, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01226 Permanent Service4/11/20194/12/20194/12/2019 2:48:54 PMPPASS
Ok to energize. Neil on site Phone #: ###-#### Inspection requested via web by Garrett Collins
65k rated main, will verify available fault current in future as per 110.9 and 110.24.
p/s o/h rec ok
ELE18-02369 Permanent Service4/10/20194/12/20194/12/2019 2:12:04 PMPCANC
Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Needed rough in inspection.
ELE18-02369 Electrical Rough-In4/12/20194/12/20194/12/2019 2:11:42 PMPPASS
Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Discussed the work depth for HVAC unit on roof disconnecting means at 480 volt.
As per 110.26(A)(1) a minimum depth of 3'6" shall be present. Disconnects will have to be moved to another location.
Energize sub gear on all floors rough in ok.
ELE19-01061 Electrical Rough-In4/11/20194/12/20194/12/2019 1:18:08 PMPPASS
Phone #: ###-#### Inspection requested via web by Caleb Gaylord
Unit A only rough in ok cover
ELE19-01141 Final4/11/20194/12/20194/12/2019 11:56:21 AMAFAIL
if access is needed contact homeowner prior to inspection to meet at location @ Ryan ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON
440.6- Overcurrent shall not exceed maximum shown on name plate rating. 25 amp max 30 fuses installed.
ELE19-00642 Final4/11/20194/12/20194/12/2019 11:19:28 AMAPASS
Garage code is 1114 Phone #: ###-#### Inspection requested via web by Kevin Heideman Final ok
ELE19-00549 Final4/11/20194/12/20194/12/2019 10:29:37 AMAPASS
Final please. Thank you Phone #: ###-#### Inspection requested via web by Kyle Lott
Final ok
ELE19-00596 Electrical Rough-In4/11/20194/12/20194/12/2019 10:28:09 AMAPASS
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden
As per notes on building permit a seperate building permit and electrical permit is required for finish out of dwelling unit.
Walls and hardlids of dwelling unit rough in ok cover
ELE19-01199 Rough-In Permanent Service4/11/20194/12/20194/12/2019 8:55:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok