Inspections for the day of: Wednesday, April 18, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00402 Final4/18/20184/18/20184/18/2018 3:23:47 PMPFAIL
Phone #: ###-#### Inspection requested via web by Nick Larson
406.6- Receptacles installed on a ungrounded circuit shall have GFCI protection or a 2 wire receptacle installed.
406.12- Island receptacle shall be tamper resistant type.
422.30- Hood shall have a disconnecting means, switch on unit did not operate.
ELE17-01032 Final4/18/20184/18/20184/18/2018 1:02:00 PMANH
Final for Units 120, 122, 123, 124, 125, 126, 128, 130, 132
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Called contact, no answer, left message to recall when someone is available
ELE18-01205 Electrical Rough-In4/17/20184/18/20184/18/2018 11:59:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
NW off elevator lobby has wiring and boxes above hardlid NR, Conference soffit, SE entry off elevator lobby, and east corridor hardlid rough in ok cover
ELE18-01470 Electrical Rough-In4/17/20184/18/20184/18/2018 11:36:55 AMAPASS
Please call Cory Hayes Phone #: ###-#### Inspection requested via web by Kevin Perez
Discussed conference rooms. Walls and hardlid as noted, few not ready, on contractor print rough in ok cover
ELE18-01462 Final4/17/20184/18/20184/18/2018 10:44:46 AMANR
Matt Murrey is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Branch circuits wiring not in place yet.
ELE18-01462 Permanent Service4/18/20184/18/20184/18/2018 10:44:11 AMPPASS
Matt Murrey is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
p/s u/g n ok
ELE18-01411 Rough-In Permanent Service4/17/20184/18/20184/18/2018 10:26:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok
ELE17-02155 Final4/17/20184/18/20184/18/2018 10:04:26 AMAFAIL
We are not currently on site. Please call Frank 30 minutes prior to arrival so he can meet you. Phone #: ###-#### Inspection requested via web by Kelly Tarter Chiller disconnecting means shall be located at a readily accessible location below 6'7". Handle on units shall have a platform built below operable handle so handle location 6'7" or lower.
ELE18-00450 Electrical Rough-In4/17/20184/18/20184/18/2018 9:41:52 AMAPASS
We are requesting a pole base inspection for tomorrow morning. Our contact is Rod @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate
Discussed if could get temp final ok prior to overhead feed to adjacent house not raised to code compliant clearance. As per Daryl DeGrange ok to barricade area off where wiring is too low until pole set and raised. Pole bases rough in ok cover
ELE18-01410 Rough-In Permanent Service4/17/20184/18/20184/18/2018 9:08:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok
ELE18-00252 Final4/16/20184/18/20184/17/2018 3:20:06 PMACANC
Chris is the contact his cell no is ###-#### Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates