ELE13-00855
| ELE-Aging Inspection | 4/23/2015 | 4/23/2015 | 4/24/2015 3:36:34 PM | | CANC |
|
|
too busy
|
ELE15-00945
| Final | 4/23/2015 | 4/23/2015 | 4/23/2015 3:47:17 PM | P | PASS |
|
|
Robert Phone #: ###-#### Final ok
|
ELE15-01133
| Temporary Service | 4/23/2015 | 4/23/2015 | 4/23/2015 3:20:47 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by mark hood t/s o/h n ok
|
ELE15-00774
| Rough-In Permanent Service | 4/22/2015 | 4/23/2015 | 4/23/2015 3:12:20 PM | P | PART |
|
|
We will be ready by 1:00 or 2:00 PM... I will call around noon to verify our progress. Thank you... Phone #: ###-#### Inspection requested via web by JOHN MCCURDY Will come by next day to confirm make up and dry sheet peak of roof do to storm expected. OK foam seal.
|
ELE15-01125
| Rough-In Permanent Service | 4/23/2015 | 4/23/2015 | 4/23/2015 2:24:43 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer Idaho Power requires an expansion joint in service riser. 300.4- NM cable shall be protected by nail plates when ran through holes less than 1 1/4" from framing surface or notched wood. 334.23- NM cable shall be protected from physical damage when ran in an accessible attic within 7' of attic access. 110.12(B)- Loose neutral in panel.
|
ELE15-00944
| Final | 4/23/2015 | 4/23/2015 | 4/23/2015 1:51:43 PM | P | FAIL |
|
|
Robert Phone #: ###-#### 250.132- Short sections of raceway shall be connected to an equipment grounding conductor. * Heat pump shall be set prior to final.
|
ELE15-01099
| Conference | 4/22/2015 | 4/23/2015 | 4/23/2015 1:20:00 PM | P | DONE |
|
|
Randall Phone #: ###-#### Discussed remodel of upstairs bathrooms and new kitchen peninsula. New receptacles for peninsula off existing kitchen appliance or new circuit. required 20 amp for bathroom receptacles, closet light placement, floor line receptacles for bed wall.
|
ELE14-02819
| Permanent Service | 4/23/2015 | 4/23/2015 | 4/23/2015 12:37:09 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Correction made p/s u/g n ok House panel
|
ELE15-00757
| Final | 4/23/2015 | 4/23/2015 | 4/23/2015 12:20:13 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
ELE15-01113
| Electrical Rough-In | 4/22/2015 | 4/23/2015 | 4/23/2015 10:54:04 AM | A | PASS |
|
|
Contact: Seth Stears. Ceiling cover in kitchen. Phone #: ###-#### Inspection requested via web by Seth Stears Hardlid in new dining area rough in ok cover
|
ELE15-01095
| Electrical Rough-In | 4/21/2015 | 4/23/2015 | 4/23/2015 10:10:04 AM | A | PASS |
|
|
Contact: Cody Cannon, rough-in, walls only Phone #: ###-#### Inspection requested via web by Deb Gooden Discussed grounding electrodes for new service and posting available fault current before permanent service. Ordered 65k breakers. transformer very close. Wall rough in ok cover
|
ELE15-01124
| Electrical Rough-In | 4/23/2015 | 4/23/2015 | 4/23/2015 9:09:33 AM | A | PASS |
|
|
Please call David Kubik at ###-#### if needed Phone #: ###-#### Inspection requested via web by Charmel Kubik Kitchen rough in ok cover
|
ELE15-00931
| Rough-In Permanent Service | 4/22/2015 | 4/23/2015 | 4/23/2015 8:45:33 AM | A | PASS |
|
|
Please contact Cody ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
|