Inspections for the day of: Friday, April 26, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01417 Permanent Service4/26/20194/26/20194/26/2019 3:18:34 PMPPASS
Owner to replace grounding electrode to underground water pipe with #4 ground as per 250.66 and secure panel to wall better.
p/s o/h rec ok
ELE19-01521 Electrical Rough-In4/26/20194/26/20194/26/2019 3:14:25 PMPPASS
Please call 30 min prior ###-#### Jimmy Phone #: ###-#### Inspection requested via web by John Edwards
Lighting mostly surface mount wiring. Columns and fireplace rough in ok cover
ELE18-04492 Permanent Service4/20/20194/26/20194/26/2019 1:58:20 PMPPASS
Scheduled disconnect with Idaho power for 9-10AM. Phone #: ###-#### Inspection requested via web by Jesse Hanson
p/s u/g rec ok
ELE19-00602 Electrical Rough-In4/26/20194/26/20194/26/2019 1:57:45 PMPPASS
UG inspection. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
East parking garage underground roug in ok cover.
ELE18-01391 Final4/26/20194/26/20194/26/2019 1:16:48 PMPPART
Contact Scott Grisbaum for final inspection on level 4. Phone #: ###-#### Inspection requested via web by Tom Betty
All items from 4-23-19 exept kitchen completed, Level 2, 3, 4, procedure lights, rm 268 GFCI protection, Damaged circuits 4NLF 24,26. TCO for these areas ok
ELE19-01435 Final4/22/20194/26/20194/26/2019 11:06:37 AMANH
small addition to solar array complete per stamped/approved plans. The homeowner will be home to give access to the garage/electrical panel.
Give the customer a call at ###-#### on your way out.
Give me a call if you have any questions about the work, ###-####.
Thanks guys Phone #: ###-#### Inspection requested via web by Ryan King
Called contact as directed, no answer, owner called after had left area, must recall
ELE19-01173 Final4/25/20194/26/20194/26/2019 10:47:07 AMAFAIL
Final Inspection Please Any Questions Please Call Louis ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller
680.26- All metallic non current carrying metal located with in 5' horizontal and 12' vertical ov water edge shall be bonded to equipment with #8 sollid conductor. Rain gutter.
ELE19-00632 Final4/25/20194/26/20194/26/2019 10:25:44 AMAPASS
Garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE19-01194 Final4/25/20194/26/20194/26/2019 9:48:30 AMAPASS
Door lock box code: 5584 Phone #: ###-#### Inspection requested via web by Nick Avery Final ok
ELE18-01608 Electrical Rough-In4/25/20194/26/20194/26/2019 9:31:14 AMAPASS
ceiling inspection at terrarium Phone #: ###-#### Inspection requested via web by Mike McCarrel
Area noted grid rough in ok cover.
ELE18-02369 Electrical Rough-In4/25/20194/26/20194/26/2019 9:10:20 AMAPASS
1st floor vestibules. Call Joey C, prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
HVAC to be installed after cover. Rough in ok cover.