ELE13-00908
| ELE-Aging Inspection | 4/27/2015 | 4/27/2015 | 5/1/2015 3:54:39 PM | | DONE |
|
|
Waiting on owner
|
ELE13-00903
| ELE-Aging Inspection | 4/27/2015 | 4/27/2015 | 5/1/2015 3:53:54 PM | | DONE |
|
|
Called contact listed with permit. She stated the work was more than they wanted to take on so spa contractor hired someone to do work no permit found. will check next week.
|
ELE13-00889
| ELE-Aging Inspection | 4/27/2015 | 4/27/2015 | 4/27/2015 3:56:00 PM | | DONE |
|
|
Permit search showed permit that covered corrections
|
ELE13-00889
| Final | 4/27/2015 | 4/27/2015 | 4/27/2015 3:53:26 PM | P | PASS |
|
|
Permit ELE13-00919 covers corrections. Final ok
|
ELE15-01063
| Final | 4/27/2015 | 4/27/2015 | 4/27/2015 3:43:46 PM | P | FAIL |
|
|
Jim Phone #: ###-#### Permit does not exist at time of inspection for corrections of unsafe conditions. Called contractor told to pull permit for work performed.
|
ELE15-00818
| Electrical Rough-In | 4/27/2015 | 4/27/2015 | 4/27/2015 2:46:15 PM | P | PASS |
|
|
Office Max, wall rough in. Contact Travis Hust Phone #: ###-#### Inspection requested via web by Cathy Duchek Office 505 wall rough in ok cover
|
ELE15-00740
| Electrical Rough-In | 4/27/2015 | 4/27/2015 | 4/27/2015 1:57:57 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Addition and back patio rough in ok cover
|
ELE15-01158
| Temporary Service | 4/27/2015 | 4/27/2015 | 4/27/2015 1:10:55 PM | P | PASS |
|
|
Located at back of property Phone #: ###-#### Inspection requested via web by kendall bender t/s o/h n ok
|
ELE15-01147
| Electrical Rough-In | 4/27/2015 | 4/27/2015 | 4/27/2015 12:31:04 PM | P | PASS |
|
|
rough in on lighting retrofit Phone #: ###-#### Inspection requested via web by Tim Dunlop Retro kits for repair bays, ballasts, disconnects, and wall packs on northside UL listings confirmed. Rough in ok cover
|
ELE15-01157
| Rough-In Permanent Service | 4/27/2015 | 4/27/2015 | 4/27/2015 10:24:55 AM | A | PASS |
|
|
gary is the contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson rough in ok cover p/s u/g n ok
|
ELE15-00046
| Final | 4/25/2015 | 4/27/2015 | 4/27/2015 9:52:35 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Dan Rohl House ok pending hot tub hook up
|
ELE15-00426
| Final | 4/24/2015 | 4/27/2015 | 4/27/2015 9:31:51 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 110.3- wiring shall be attached as per listing. reverse polarity master bed. 314.21- Drywall shall be repaired around boxes so no gap shall be more than 1/8" at edge of box.
|
ELE15-01156
| Rough-In Permanent Service | 4/27/2015 | 4/27/2015 | 4/27/2015 8:33:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Robert Schroder Rough in ok cover p/s u/g n ok
|