ELE20-00075
| Electrical Rough-In | 4/6/2020 | 4/6/2020 | 4/6/2020 2:24:59 PM | P | PASS |
|
|
Rough in for second floor Phone #: ###-#### Inspection requested via web by Zane Robertson Discussed if medical wiring method needed, tamper requirements, no lighting below 7'6", commissioning report for lighting control system. Contractor ran medical grade wiring method in all rooms for therapy. Confirmed city approved set of prints on site. Level 2 walls and hardlids rough in ok cover.
|
ELE20-01170
| Electrical Rough-In | 4/2/2020 | 4/6/2020 | 4/6/2020 1:51:09 PM | P | PASS |
|
|
Underground Inspection, Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Underground to new service on north east corner rough in ok cover
|
ELE19-03884
| Final | 4/3/2020 | 4/6/2020 | 4/6/2020 12:54:00 PM | P | FAIL |
|
|
Final inspection Please. Have a bless week. Phone #: ###-#### Inspection requested via web by Kyle Lott 110.12(A)- Unused openings shall be closed by approved means. Ceiling bell boxes have open knock outs. 110.22- Required structure disconnecting means shall be labeled. 225.32- Required structure disconnecting means shall be installed in a readily accessible location. Mounted at same height as exit signs. BCC 4-05-23- Unlawful to cover in any way electrical installation. Must expose 2 locations of underground conduit to bike enclosure to verify depth.
|
ELE20-01208
| Permanent Service | 4/5/2020 | 4/6/2020 | 4/6/2020 9:38:54 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake Needed temp service inspection
|
ELE20-01208
| Temporary Service | 4/6/2020 | 4/6/2020 | 4/6/2020 9:38:27 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake t/s u/g n ok
|
ELE20-01209
| Permanent Service | 4/5/2020 | 4/6/2020 | 4/6/2020 9:36:13 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake Needed temp service inspection
|
ELE20-01209
| Temporary Service | 4/6/2020 | 4/6/2020 | 4/6/2020 9:34:42 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake t/s u/g n ok
|