Inspections for the day of: Monday, April 6, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00075 Electrical Rough-In4/6/20204/6/20204/6/2020 2:24:59 PMPPASS
Rough in for second floor Phone #: ###-#### Inspection requested via web by Zane Robertson
Discussed if medical wiring method needed, tamper requirements, no lighting below 7'6", commissioning report for lighting control system.
Contractor ran medical grade wiring method in all rooms for therapy.
Confirmed city approved set of prints on site.
Level 2 walls and hardlids rough in ok cover.
ELE20-01170 Electrical Rough-In4/2/20204/6/20204/6/2020 1:51:09 PMPPASS
Underground Inspection, Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Underground to new service on north east corner rough in ok cover
ELE19-03884 Final4/3/20204/6/20204/6/2020 12:54:00 PMPFAIL
Final inspection Please. Have a bless week. Phone #: ###-#### Inspection requested via web by Kyle Lott
110.12(A)- Unused openings shall be closed by approved means. Ceiling bell boxes have open knock outs.
110.22- Required structure disconnecting means shall be labeled.
225.32- Required structure disconnecting means shall be installed in a readily accessible location. Mounted at same height as exit signs. BCC 4-05-23- Unlawful to cover in any way electrical installation. Must expose 2 locations of underground conduit to bike enclosure to verify depth.
ELE20-01208 Permanent Service4/5/20204/6/20204/6/2020 9:38:54 AMACANC
Phone #: ###-#### Inspection requested via web by Ryan Wake
Needed temp service inspection
ELE20-01208 Temporary Service4/6/20204/6/20204/6/2020 9:38:27 AMPPASS
Phone #: ###-#### Inspection requested via web by Ryan Wake t/s u/g n ok
ELE20-01209 Permanent Service4/5/20204/6/20204/6/2020 9:36:13 AMACANC
Phone #: ###-#### Inspection requested via web by Ryan Wake
Needed temp service inspection
ELE20-01209 Temporary Service4/6/20204/6/20204/6/2020 9:34:42 AMPPASS
Phone #: ###-#### Inspection requested via web by Ryan Wake t/s u/g n ok