Inspections for the day of: Thursday, May 2, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01486 Permanent Service5/2/20195/2/20195/2/2019 2:44:38 PMPPASS
Changing out meter/panel box. IPCO is requiring inspection before they will re-energize. This is an occupied residence. Can you please arrange to inspect latter this afternoon so power can be restored today, thanks. Phone #: ###-#### Inspection requested via web by Brandon Winters
p/s o/h rec ok
ELE19-00831 Final5/1/20195/2/20195/2/2019 2:02:32 PMPPASS
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Final ok
ELE18-04652 Final5/1/20195/2/20195/2/2019 1:21:59 PMPNR
Phone #: ###-#### Inspection requested via web by Tyler Stewart
For electrical final inspection all covers must be installed, devices operational, and exposed wiring below 8' shall be protected from accidental contact.
All device wiring checked out ok, Wall cover for fireplace build out not installed with exposed wiring all around fireplace.
Recall when all wall cover and device covers installed and ready to use.
ELE19-01583 Temporary Service5/1/20195/2/20195/2/2019 11:50:59 AMAFAIL
temporary service for construction site.
Shannon is the contact person. Phone #: ###-#### Inspection requested via web by Shawna Gates
210.21- Overcurrent protection shall not axceed rating of receptacle. 40 amp installed.
590.6- All receptacles other than 120 volt shall have GFCI protection. Standard 240 installed on 50 amp receptacle.
ELE19-00831 Electrical Rough-In5/1/20195/2/20195/2/2019 11:22:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher
Listing and disconnecting means confirmed rough in ok
ELE19-00777 Final5/1/20195/2/20195/2/2019 10:52:47 AMAFAIL
garage code should be 0425 Phone #: ###-#### Inspection requested via web by Neal Rumsey
314.16- Boxes shall have adequate space for conductors installed. Island receptacle has 11.25 cubic inches of conductor installed in a 8 cubic inch box.
ELE19-01595 Electrical Rough-In5/1/20195/2/20195/2/2019 9:44:12 AMAPASS
Homeowner will be home in am. His name is Jeff Wirht. Phone #: ###-#### Inspection requested via web by Craig Korell
Kitchen and laundry rough in k cover
ELE19-01540 Electrical Rough-In4/30/20195/2/20195/2/2019 9:16:11 AMAPASS
Contact Bruce Thorpe @ ###-#### with any questions

Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Wall rough in ok cover
ELE19-00817 Electrical Rough-In5/1/20195/2/20195/2/2019 8:59:51 AMAPASS
Ceiling inspection for cover
Phil is the contact
North Face Phone #: ###-#### Inspection requested via web by Shawna Gates
Dressing rooms and entrance lids rough in ok cover