Inspections for the day of: Friday, May 3, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00672 Final5/2/20195/3/20195/3/2019 3:08:59 PMPFAIL
Will be on site all day Phone #: ###-#### Inspection requested via web by robert feller
110.3- Misc receptacles not working on south or cable walls.
110.26(D)- Luminaires installed for required illumination for electrical equipment shall not operate by automatic means. Remove motion sensors.
210.8(B)(7)- All 15 or 20 amp receptacle outlets located in locker rooms associated with shower areas shall have GFCI protection. TV receptacles. 250.64(E)- Grounding electrode conductors installed in ferrous metal raceways shall clamp to conductor at each end by fittings for clamps.
314.20- Where boxes are recessed in non combustible wall cover 1/4" or more they shall have spark rings installed. Bathrooms, south or cable walls.
700.3- Emergency lighting and exit signs shall operate when tested.
ELE19-01583 Temporary Service5/3/20195/3/20195/3/2019 2:44:46 PMPPASS
3rd time is a charm. Phone #: ###-#### Inspection requested via web by Shawna Gates t/s o/h n ok
ELE18-00602 Electrical Rough-In5/3/20195/3/20195/3/2019 1:26:41 PMPPASS
John- ceiling electrical inspection Phone #: ###-####
Hospital side grid, all except storage room. Exam or surgical lights have support system in but not luminaires. Rest of grid in this area rough in ok cover
ELE19-01261 Electrical Rough-In5/3/20195/3/20195/3/2019 11:35:54 AMAPASS
Inspection requested via web by Brad Girard
Portion of basement taken apart for concrete pour. Inspection for rewiring of area.
South basement area walls and ceiling rough in ok cover.
ELE19-01342 Temporary Service5/3/20195/3/20195/3/2019 10:56:45 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M
t/s o/h n ok
ELE18-01935 Electrical Rough-In5/2/20195/3/20195/3/2019 10:18:44 AMAPASS
Unit 412 fire place
Unit 407 fire place
2nd floor hall way
Contact John (Homey) McElroy
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Discussed LED rope or tape lighting to penatrate ceiling to get to other side of bathroom would depend on manufacturers instructions if approved for such installation. Each bathroom receptacle is fed by dedicated circuits so could have LED lighting on with basin receptacle as per 210.11(C)(3).
Units 407and 412 fireplaces and level 2 hall ceilings rough in ok cover.
ELE19-00288 Final5/2/20195/3/20195/3/2019 9:16:52 AMAPASS
Contact - Neil Adams ###-#### Phone #: ###-#### Inspection requested via web by Todd Alder
No card posted. Final ok
ELE19-01583 Temporary Service5/2/20195/3/20195/3/2019 8:26:00 AMAFAIL
Shannon is the contact again Phone #: ###-#### Inspection requested via web by Shawna Gates
Corrections not complete