Inspections for the day of: Thursday, May 30, 2013.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00368 ELE-Aging Inspection5/30/20135/30/20135/30/2013 3:56:53 PM DONE
Still waiting on owner
ELE13-00393 Final5/30/20135/30/20135/30/2013 3:28:06 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson
Final ok
ELE13-01311 Rough-In Permanent Service5/30/20135/30/20135/30/2013 2:52:23 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by daniel bibikov
300.4- Protection from physical damage, washer, dryer, furnace wires plus misc through out.
250.110- Non current carrying metal parts shall be connected to equiptment grounding conductor.
300.3(C)- Conductors shall have an insulating rating equal to the maximum circuit voltage applied to any conductor with in enclosure.
ELE13-01361 Electrical Rough-In5/30/20135/30/20135/30/2013 2:22:06 PMPPASS
Please call 30 min prior to inspection. Phone #: ###-#### >> Inspection requested via web by Camille Gulley wall rough in ok cover
ELE13-00388 Final5/30/20135/30/20135/30/2013 1:18:33 PMPNR
Final on main level only. Thank you Phone #: ###-#### >> Inspection requested via web by Eric Brown Covers, labelling, wp inaccessible, not all breakers installed.
ELE13-01360 Electrical Rough-In5/30/20135/30/20135/30/2013 12:34:31 PMPPASS
CALL FOR ACCESS Phone #: ###-#### >> Inspection requested via web by John VanZandt
Kitchen, misc lighting, and baths remodel rough in ok cover.
ELE13-01354 Temporary Service5/29/20135/30/20135/30/2013 10:31:11 AMPFAIL
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman
250.24(A)- Grounding electrode conductor connection shall be made at the same terminal or bus as grounded conductor.
110.7- GFCI receptical on right has test button stuck in depressed state. Replace.
Remove debris from mater base.
ELE13-01133 Final5/29/20135/30/20135/30/2013 10:25:43 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey
final ok
ELE13-00866 Final5/29/20135/30/20135/30/2013 10:00:11 AMAPASS
Call Jim (###-####) 30 min ahead for access Phone #: ###-#### >> Inspection requested via web by Brad Girard Final ok
ELE13-00609 Final5/29/20135/30/20135/30/2013 9:45:34 AMAPASS
Call Jim (###-####) 30 min ahead for access Phone #: ###-#### >> Inspection requested via web by Brad Girard Final ok
ELE12-02982 Electrical Rough-In5/29/20135/30/20135/30/2013 9:22:08 AMAPASS
Tony Phone #: ###-#### Ceiling pour noted on print rough in ok cover
ELE13-00977 Final5/29/20135/30/20135/30/2013 8:52:25 AMAPASS
Kevin Phone #: ###-#### Final ok
ELE13-01351 Temporary Service5/29/20135/30/20135/29/2013 1:38:04 PMAPASS
READY NOW Phone #: ###-#### >> Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE13-01352 Temporary Service5/29/20135/30/20135/29/2013 1:36:33 PMAPASS
READY NOW Phone #: ###-#### >> Inspection requested via web by Bob Glenn
t/s u/g n ok