ELE20-01889
| Final | 6/16/2020 | 6/17/2020 | 6/17/2020 4:39:36 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Same Electric Final ok
|
ELE19-03829
| Electrical Rough-In | 6/16/2020 | 6/17/2020 | 6/17/2020 4:13:01 PM | P | PASS |
|
|
Wall rough-in inspection. Contact electrician Shawn Evins. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek NW, SW corridors, fire riser rm, generator rm, bike rm, managers office, com rm, walls as noted on contractor print rough in ok cover.
|
ELE20-01344
| Electrical Rough-In | 6/16/2020 | 6/17/2020 | 6/17/2020 3:48:13 PM | P | CANC |
|
|
Cooper - later is better Phone #: ###-#### Changed to a conference to fine tune install.
|
ELE20-01344
| Conference | 6/17/2020 | 6/17/2020 | 6/17/2020 3:47:59 PM | P | PASS |
|
|
Cooper - later is better Phone #: ###-#### Walked complete house and discussed all areas for layout and circuitry. Pamphlet given. Existing church in it entirety to be converted into a dwelling unit. Owner good understanding on scope of work.
|
ELE20-00609
| Final | 6/16/2020 | 6/17/2020 | 6/17/2020 2:32:06 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.3- Lower patio outdoor receptacle shows open ground. 210.8(A)- All 15 and 20 amp receptacle outlets located with in 6' of a sink shall have GFCI protection. 210.51(A)- All wall space 2' or wider shall have a receptacle outlet installed. down bed by door. 210.70- Required luminaired for rooms and outdoors near mandoors shall operate. Programming. 410.10- Securely mounted wall lights with in 3' of master bath tub shall be damp location rated.
|
ELE20-00016
| Final | 6/17/2020 | 6/17/2020 | 6/17/2020 1:35:08 PM | P | FAIL |
|
|
Lockbox code is 3697 Phone #: ###-#### Inspection requested via web by Troy Cobb 406.4(D)- Grounding type receptacles installed on ungrounded circuits shall have GFCI proteciton
|
ELE20-02052
| Rough-In Permanent Service | 6/16/2020 | 6/17/2020 | 6/17/2020 12:22:33 PM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey No service at this time just dwelling rough in.
|
ELE20-02052
| Electrical Rough-In | 6/17/2020 | 6/17/2020 | 6/17/2020 12:22:17 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Overhead 2 pack meter pack service change to be done in future. New unit rough in ok cover.
|
ELE19-03017
| Final | 6/17/2020 | 6/17/2020 | 6/17/2020 11:38:43 AM | A | PART |
|
|
FINAL MEZZANINE AND ELECTRICAL ROOM Phone #: ###-#### Inspection requested via web by Debby Pierce No heat tape installed yet, did not test EPD breakers. 110.26- Work space height shall be provided for area A Mezz. Panel M1.Line sets at 6' 28" in front of panel, 6'6" required, TCO for areas noted ok
|
ELE20-00575
| Rough-In Permanent Service | 6/17/2020 | 6/17/2020 | 6/17/2020 10:57:54 AM | A | PASS |
|
|
Thank You Phone #: ###-#### Inspection requested via web by Eric Brown Rough in ok cover p/s u/g n ok
|
ELE20-02053
| Conference | 6/17/2020 | 6/17/2020 | 6/17/2020 10:16:13 AM | A | PASS |
|
|
Site Contact is HP Honeycutt. Would like to review existing conditions with AHJ and determine what existing is acceptable to remain. Thank you Phone #: ###-#### Inspection requested via web by Steve Blackmer 3 bedroom areas no planned upgrades ok to remain and refeed, and minimum work space shall be provided for bsement sub panel location, may be a little tight on height.
|
ELE20-01672
| Electrical Rough-In | 6/17/2020 | 6/17/2020 | 6/17/2020 9:32:46 AM | A | PASS |
|
|
Floor heat rough in only in Master Bathroom. Garage code is #3283 Phone #: ###-#### Inspection requested via web by Nermin Bobaric Floor heat rough in ok cover
|
ELE20-00894
| Final | 6/16/2020 | 6/17/2020 | 6/17/2020 9:27:48 AM | A | PASS |
|
|
I’ll meet you there to walk through inspection, thank you Phone #: ###-#### Inspection requested via web by Keith Chetta Final ok
|
ELE20-01782
| Final | 6/17/2020 | 6/17/2020 | 6/17/2020 9:08:58 AM | A | NR |
|
|
Please call Bruce when you arrive on site.
Thank you ; have a great day! Phone #: ###-#### Inspection requested via web by JENNY EMEL Receptacle operational but no GFCI protection as required by 210.8(B).
|
ELE20-01672
| Electrical Rough-In | 6/16/2020 | 6/17/2020 | 6/17/2020 12:08:16 AM | A | CANC |
|
|
Floor heat in master bathroom Phone #: ###-#### >> Inspection requested via web by Nermin Bobaric Inspection cancelled from web by: Nermin Bobaric
|