ELE19-02244
| Electrical Rough-In | 6/18/2019 | 6/18/2019 | 6/18/2019 2:40:25 PM | P | PASS |
|
|
Underground to cover conduits Phone #: ###-#### Inspection requested via web by Stan Woodward Underground rough in ok cover
|
ELE19-01604
| Electrical Rough-In | 6/18/2019 | 6/18/2019 | 6/18/2019 2:20:00 PM | P | PASS |
|
|
Pony wall Phone #: ###-#### Inspection requested via web by Bryan McLaughlin Area noted rough in ok cover
|
ELE19-00602
| Electrical Rough-In | 6/18/2019 | 6/18/2019 | 6/18/2019 1:58:53 PM | P | PASS |
|
|
Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen EMT being used with taped up boxes and fittings as per instructions. Bottom of ramp pour rough in ok cover
|
ELE19-00433
| Final | 6/18/2019 | 6/18/2019 | 6/18/2019 1:47:04 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mike McCarrel Bldg E-1 Hornbill exibit final ok
|
ELE19-00881
| Permanent Service | 6/17/2019 | 6/18/2019 | 6/18/2019 12:08:11 PM | A | FAIL |
|
|
Please call before you head to the site Phone #: ###-#### Inspection requested via web by Spencer McLean 408.7- Unused breaker spaces shall be closed by approved means. Breaker blank needed.
|
ELE19-02222
| Final | 6/17/2019 | 6/18/2019 | 6/18/2019 11:50:19 AM | A | PASS |
|
|
Home owner should be home. Panel is on back of house. A/c is on west side Phone #: ###-#### Inspection requested via web by Jake Cutler Final ok
|
ELE19-01028
| Permanent Service | 6/17/2019 | 6/18/2019 | 6/18/2019 11:30:36 AM | A | CANC |
|
|
Please call before heading to the site. Phone #: ###-#### Inspection requested via web by Spencer McLean Needed final inspection.
|
ELE19-01028
| Final | 6/18/2019 | 6/18/2019 | 6/18/2019 11:30:26 AM | P | FAIL |
|
|
Please call before heading to the site. Phone #: ###-#### Inspection requested via web by Spencer McLean 408.7- Unused breaker spaces shall be closed by approved means. Breaker blank needed in panel at base of pole.
|
ELE19-00594
| Final | 6/17/2019 | 6/18/2019 | 6/18/2019 11:18:23 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Devices shall be wired as per manufacturers instructions. Reverse polarity in laundry. 210.8(A)(2)- Unfinished space off garage receptacles shall have GFCI protection. 314.16- Boxes shall have sufficient subic inch rating for conductors installed. Island receptacle box 8 cubic inches with 11.25 of conductor cubic inch installed. 348.30- FMC shall be secured with in 12" of a termination. Furnace, disposal. 406.5- Master bed USB receptacle shall be flush or project from face plate.
|
ELE19-01635
| Final | 6/17/2019 | 6/18/2019 | 6/18/2019 10:28:23 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Steven Ragan 358.42- Couplings and connectors shall be made tight. Several loose.
|
ELE19-01453
| Final | 6/17/2019 | 6/18/2019 | 6/18/2019 10:12:12 AM | A | PASS |
|
|
thr key code is 4040 Thanks Phone #: ###-#### Inspection requested via web by brian morrow Final ok
|