ELE19-04799
| Conference | 6/18/2020 | 6/18/2020 | 6/18/2020 3:22:08 PM | P | PASS |
|
|
Need to discuss auxiliary gutters at meter pak main disconnects Phone #: ###-#### Inspection requested via web by Jason Parke Discussed the use of an auxiliary gutter to extend form the bottom of main disconnecting means down to where service entrance conduits are miss- aligned with botton of disconnect. As per the definition auxiliar gutter is a sheet metal or non metallic gutter is use to extend a piece of equipment to provide additional wiring space. Service entrance conduits will be encased in concrete to the entry of the main disconnect extension or auxiliary gutter in compliance with 230.6 or concidered outside of structure. Auxiliary gutter ok to use.
|
ELE20-00609
| Final | 6/17/2020 | 6/18/2020 | 6/18/2020 2:26:58 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
|
ELE20-02071
| Temporary Service | 6/18/2020 | 6/18/2020 | 6/18/2020 1:34:04 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard t/s u/g n ok
|
ELE20-02072
| Temporary Service | 6/18/2020 | 6/18/2020 | 6/18/2020 1:33:36 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard t/s u/g n ok
|
ELE20-02030
| Final | 6/17/2020 | 6/18/2020 | 6/18/2020 12:58:07 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder Final ok.
|
ELE20-01994
| Electrical Rough-In | 6/17/2020 | 6/18/2020 | 6/18/2020 11:47:27 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Andy Chambers Concrete encased at main service and fire riser room and service entrance conduits at main service location rough in ok cover.
|
ELE20-01666
| Final | 6/17/2020 | 6/18/2020 | 6/18/2020 11:13:53 AM | A | NR |
|
|
call for access Phone #: ###-#### Inspection requested via web by Chris Berthelot Occupied house, must be someone here to inspect.
|
ELE20-00016
| Final | 6/17/2020 | 6/18/2020 | 6/18/2020 11:02:56 AM | A | PASS |
|
|
Installed GFI protection for ungrounded 3-prong outlets in bedrooms and Living room. Lockbox code is 3697 Phone #: ###-#### Inspection requested via web by Troy Cobb Final ok
|
ELE19-04204
| Final | 6/17/2020 | 6/18/2020 | 6/18/2020 10:42:05 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.3- Pantry light not working. 250.94- An intersystem bond shall be installed for utilities. 314.25- All boxes and devices shall have covers. Areas with tile have cover and devices removed. 352.30- PVC service riser shall be secured with in 3' of meter base. 422.30- Appliances shall have an accessible disconnecting means. 110.25 lock outs acceptable. Dishwasher and micro. 680.51- Fountain shall have GFCI protection for pump
|
ELE20-01937
| Rough-In Permanent Service | 6/17/2020 | 6/18/2020 | 6/18/2020 9:29:21 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve sellers Service calculation by contractor =174 amps. Rough in ok cover p/s o/h n ok
|
ELE19-01588
| Final | 6/18/2020 | 6/18/2020 | 6/18/2020 8:49:57 AM | A | FAIL |
|
|
Wire a compactor circuit in te back of the building Phone #: ###-#### Inspection requested via web by Greg Idsinga 110.26- Work space shall be provided for disconnecting means of 30" wide x 36" deep minimum. Disconnect located directly behind unit with 10" clearance.
|