Inspections for the day of: Thursday, June 18, 2020.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04799 Conference6/18/20206/18/20206/18/2020 3:22:08 PMPPASS
Need to discuss auxiliary gutters at meter pak main disconnects Phone #: ###-#### Inspection requested via web by Jason Parke
Discussed the use of an auxiliary gutter to extend form the bottom of main disconnecting means down to where service entrance conduits are miss- aligned with botton of disconnect. As per the definition auxiliar gutter is a sheet metal or non metallic gutter is use to extend a piece of equipment to provide additional wiring space. Service entrance conduits will be encased in concrete to the entry of the main disconnect extension or auxiliary gutter in compliance with 230.6 or concidered outside of structure. Auxiliary gutter ok to use.
ELE20-00609 Final6/17/20206/18/20206/18/2020 2:26:58 PMPPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
ELE20-02071 Temporary Service6/18/20206/18/20206/18/2020 1:34:04 PMPPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard t/s u/g n ok
ELE20-02072 Temporary Service6/18/20206/18/20206/18/2020 1:33:36 PMPPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard t/s u/g n ok
ELE20-02030 Final6/17/20206/18/20206/18/2020 12:58:07 PMAPASS
Phone #: ###-#### Inspection requested via web by Eric Schroeder Final ok.
ELE20-01994 Electrical Rough-In6/17/20206/18/20206/18/2020 11:47:27 AMAPASS
Phone #: ###-#### Inspection requested via web by Andy Chambers Concrete encased at main service and fire riser room and service entrance conduits at main service location rough in ok cover.
ELE20-01666 Final6/17/20206/18/20206/18/2020 11:13:53 AMANR
call for access Phone #: ###-#### Inspection requested via web by Chris Berthelot Occupied house, must be someone here to inspect.
ELE20-00016 Final6/17/20206/18/20206/18/2020 11:02:56 AMAPASS
Installed GFI protection for ungrounded 3-prong outlets in bedrooms and Living room. Lockbox code is 3697 Phone #: ###-#### Inspection requested via web by Troy Cobb Final ok
ELE19-04204 Final6/17/20206/18/20206/18/2020 10:42:05 AMAFAIL
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.3- Pantry light not working. 250.94- An intersystem bond shall be installed for utilities. 314.25- All boxes and devices shall have covers. Areas with tile have cover and devices removed. 352.30- PVC service riser shall be secured with in 3' of meter base. 422.30- Appliances shall have an accessible disconnecting means. 110.25 lock outs acceptable. Dishwasher and micro. 680.51- Fountain shall have GFCI protection for pump
ELE20-01937 Rough-In Permanent Service6/17/20206/18/20206/18/2020 9:29:21 AMAPASS
Phone #: ###-#### Inspection requested via web by steve sellers
Service calculation by contractor =174 amps. Rough in ok cover p/s o/h n ok
ELE19-01588 Final6/18/20206/18/20206/18/2020 8:49:57 AMAFAIL
Wire a compactor circuit in te back of the building Phone #: ###-#### Inspection requested via web by Greg Idsinga 110.26- Work space shall be provided for disconnecting means of 30" wide x 36" deep minimum. Disconnect located directly behind unit with 10" clearance.