Inspections for the day of: Tuesday, June 26, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01549 Final6/25/20186/26/20186/26/2018 3:09:49 PMPFAIL
Please call Shane 30 min prior so he can meet you onsite.
Shane''s cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Circuit directory for fountain control panel.
Fountain control panel transformer shall bond neutral at trans to grounding electrode a system.
Remove flexible cord and replace with structural wiring method.
ELE18-00727 Permanent Service6/25/20186/26/20186/26/2018 1:24:42 PMPPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins
p/s u/g n ok
ELE17-04065 Electrical Rough-In6/26/20186/26/20186/26/2018 1:24:12 PMPPASS
Wall Cover and ceiling on floors 1 and 2. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 1 and 2 back patios walls and emergency light and occ sensor grid rough in ok cover
ELE17-02862 Electrical Rough-In6/26/20186/26/20186/26/2018 11:57:46 AMAPASS
Units 409 , 410 , 411 , 416 and stairs 4th floor Phone #: ###-#### Inspection requested via web by Tom Betty
Rooms noted rough in ok cover
ELE18-01935 Electrical Rough-In6/26/20186/26/20186/26/2018 11:03:51 AMAPASS
Underground SE corner of building Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Service entrance conduits from tranformer to building rough in ok cover
ELE18-02080 Electrical Rough-In6/26/20186/26/20186/26/2018 10:50:21 AMAPASS
Requesting a rough in inspection. There was a change to the layout. The homeowner wanted a wall added and the light in the laundry room had to be separated from the mud room. We added a switch for the laundry room plus an outlet. Thanks Todd Phone #: ###-#### Inspection requested via web by todd cline Laundry/ mud wall rough in ok cover
ELE18-02360 Electrical Rough-In6/25/20186/26/20186/26/2018 9:06:18 AMAPASS
Phone #: ###-#### Inspection requested via web by David Boldridge
Final ok
ELE18-02360 Electrical Rough-In6/26/20186/26/20186/26/2018 9:05:57 AMPPASS
Phone #: ###-#### Inspection requested via web by David Boldridge
Addition of 1 garage receptacle rough in ok cover.
ELE18-01353 Final6/25/20186/26/20186/26/2018 8:32:26 AMACANC
Garage code is 1280 Phone #: ###-#### Inspection requested via web by TOM BICANDI
Dupicate request
ELE18-01353 Final6/25/20186/26/20186/26/2018 8:32:03 AMAPASS
Garage code is 1280 Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok