ELE15-01954
| Final | 6/30/2015 | 6/30/2015 | 6/30/2015 2:58:34 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by cory carman Final ok
|
ELE15-01978
| Conference | 6/30/2015 | 6/30/2015 | 6/30/2015 2:16:26 PM | P | DONE |
|
|
Fire damage Phone #: ###-#### Inspection requested via web by Kevin Burke Discussed how to proceed with upstairs fire damage. No damage to wiring found, no new wiring being installed. Asked to nail plate and repair stapling issues and an over filled box. All original 1972 codes apply.
|
ELE14-03133
| Electrical Rough-In | 6/29/2015 | 6/30/2015 | 6/30/2015 1:25:55 PM | P | NH |
|
|
Brad Phone #: ###-#### No answer at door unable to make contact with phone call. Left card
|
ELE15-01972
| Electrical Rough-In | 6/29/2015 | 6/30/2015 | 6/30/2015 1:06:45 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Andy Derrick 356.12(1)- LFNC shall not be installed where subject to physical damage, above ground to tub. Underground rough in ok cover
|
ELE15-01909
| Final | 6/30/2015 | 6/30/2015 | 6/30/2015 12:42:38 PM | P | CANC |
|
|
Request for inspection for ID Power to connect power to the panel. Wiring from meter to main panel will need to be done while ID Power disconnects the temp service, due to the heat load. **Please call the office for clarification** Phone #: ###-#### Inspection requested via web by Kendra Lanham Needed permenant service inspection.
|
ELE15-01909
| Permanent Service | 6/30/2015 | 6/30/2015 | 6/30/2015 12:41:57 PM | P | PASS |
|
|
Request for inspection for ID Power to connect power to the panel. Wiring from meter to main panel will need to be done while ID Power disconnects the temp service, due to the heat load. **Please call the office for clarification** Phone #: ###-#### Inspection requested via web by Kendra Lanham Due to excessive heat contractor to make interior connection so house will be out of power for minimal time. Grounding electode system to be replaced by final due to rebar exposed to weather. p/s u/g rec ok
|
ELE15-01009
| Final | 6/29/2015 | 6/30/2015 | 6/30/2015 11:39:35 AM | P | PASS |
|
|
Install 2 sets of letters reading Pearle Vision. ALL PRIMARY POWER BY OTHERS Phone #: ###-#### Inspection requested via web by Ken Olsen Unit 105 UL listing confirmed. Final ok
|
ELE15-01205
| Electrical Rough-In | 6/29/2015 | 6/30/2015 | 6/30/2015 11:20:40 AM | A | FAIL |
|
|
Please contact Travis prior to arrival. Phone #: ###-#### Inspection requested via web by Stacie Tasker Verbal with kenny on site. nail plates, support mc, secure with in 12" of boxes, repair broken jacket mc warehouse
|
ELE15-01968
| Final | 6/29/2015 | 6/30/2015 | 6/30/2015 10:23:20 AM | A | NR |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender See rough in
|
ELE15-01968
| Electrical Rough-In | 6/29/2015 | 6/30/2015 | 6/30/2015 10:21:41 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 400.8- Flexible cords shall not be used where run through bored holes in walls and ceilings, where attached to building surfaces.
|
ELE15-01729
| Rough-In Permanent Service | 6/29/2015 | 6/30/2015 | 6/30/2015 9:33:15 AM | A | CANC |
|
|
Underground ; Bonding Inspection Phone #: ###-#### Inspection requested via web by Louis Keller Needed rough in only
|
ELE15-01729
| Electrical Rough-In | 6/30/2015 | 6/30/2015 | 6/30/2015 9:32:20 AM | P | PASS |
|
|
Underground ; Bonding Inspection Phone #: ###-#### Inspection requested via web by Louis Keller Water bond located off pad for pool equipment underground with ground box for access. Bonds to perimeter, pool cover and equipment. Underground and bonding rough in ok cover.
|
ELE15-01911
| Final | 6/29/2015 | 6/30/2015 | 6/30/2015 9:12:28 AM | A | PASS |
|
|
Scope of work on this project changed we did not have to Install new meter/panel combination. We found a breaker and was able to install that. Questions please call John. Phone #: ###-#### Inspection requested via web by Celinda Winters Final ok
|
ELE15-00199
| Final | 6/29/2015 | 6/30/2015 | 6/30/2015 8:55:33 AM | A | PASS |
|
|
code #0363 Phone #: ###-#### Inspection requested via web by Eric Schroeder Final ok
|
ELE15-01969
| Temporary Service | 6/29/2015 | 6/30/2015 | 6/30/2015 8:41:07 AM | A | PASS |
|
|
Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan t/s u/g n ok
|
ELE15-01922
| Final | 6/29/2015 | 6/30/2015 | 6/29/2015 3:14:31 PM | A | CANC |
|
|
Bob Thomas Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|