Inspections for the day of: Tuesday, June 30, 2015.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01954 Final6/30/20156/30/20156/30/2015 2:58:34 PMPPASS
Phone #: ###-#### Inspection requested via web by cory carman Final ok
ELE15-01978 Conference6/30/20156/30/20156/30/2015 2:16:26 PMPDONE
Fire damage Phone #: ###-#### Inspection requested via web by Kevin Burke Discussed how to proceed with upstairs fire damage. No damage to wiring found, no new wiring being installed. Asked to nail plate and repair stapling issues and an over filled box. All original 1972 codes apply.
ELE14-03133 Electrical Rough-In6/29/20156/30/20156/30/2015 1:25:55 PMPNH
Brad Phone #: ###-#### No answer at door unable to make contact with phone call. Left card
ELE15-01972 Electrical Rough-In6/29/20156/30/20156/30/2015 1:06:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Andy Derrick 356.12(1)- LFNC shall not be installed where subject to physical damage, above ground to tub. Underground rough in ok cover
ELE15-01909 Final6/30/20156/30/20156/30/2015 12:42:38 PMPCANC
Request for inspection for ID Power to connect power to the panel. Wiring from meter to main panel will need to be done while ID Power disconnects the temp service, due to the heat load. **Please call the office for clarification** Phone #: ###-#### Inspection requested via web by Kendra Lanham Needed permenant service inspection.
ELE15-01909 Permanent Service6/30/20156/30/20156/30/2015 12:41:57 PMPPASS
Request for inspection for ID Power to connect power to the panel. Wiring from meter to main panel will need to be done while ID Power disconnects the temp service, due to the heat load. **Please call the office for clarification** Phone #: ###-#### Inspection requested via web by Kendra Lanham Due to excessive heat contractor to make interior connection so house will be out of power for minimal time. Grounding electode system to be replaced by final due to rebar exposed to weather. p/s u/g rec ok
ELE15-01009 Final6/29/20156/30/20156/30/2015 11:39:35 AMPPASS
Install 2 sets of letters reading Pearle Vision. ALL PRIMARY POWER BY OTHERS Phone #: ###-#### Inspection requested via web by Ken Olsen Unit 105 UL listing confirmed. Final ok
ELE15-01205 Electrical Rough-In6/29/20156/30/20156/30/2015 11:20:40 AMAFAIL
Please contact Travis prior to arrival. Phone #: ###-#### Inspection requested via web by Stacie Tasker Verbal with kenny on site. nail plates, support mc, secure with in 12" of boxes, repair broken jacket mc warehouse
ELE15-01968 Final6/29/20156/30/20156/30/2015 10:23:20 AMANR
Phone #: ###-#### Inspection requested via web by kendall bender See rough in
ELE15-01968 Electrical Rough-In6/29/20156/30/20156/30/2015 10:21:41 AMAFAIL
Phone #: ###-#### Inspection requested via web by kendall bender 400.8- Flexible cords shall not be used where run through bored holes in walls and ceilings, where attached to building surfaces.
ELE15-01729 Rough-In Permanent Service6/29/20156/30/20156/30/2015 9:33:15 AMACANC
Underground ; Bonding Inspection Phone #: ###-#### Inspection requested via web by Louis Keller Needed rough in only
ELE15-01729 Electrical Rough-In6/30/20156/30/20156/30/2015 9:32:20 AMPPASS
Underground ; Bonding Inspection Phone #: ###-#### Inspection requested via web by Louis Keller Water bond located off pad for pool equipment underground with ground box for access. Bonds to perimeter, pool cover and equipment. Underground and bonding rough in ok cover.
ELE15-01911 Final6/29/20156/30/20156/30/2015 9:12:28 AMAPASS
Scope of work on this project changed we did not have to Install new meter/panel combination. We found a breaker and was able to install that. Questions please call John. Phone #: ###-#### Inspection requested via web by Celinda Winters Final ok
ELE15-00199 Final6/29/20156/30/20156/30/2015 8:55:33 AMAPASS
code #0363 Phone #: ###-#### Inspection requested via web by Eric Schroeder Final ok
ELE15-01969 Temporary Service6/29/20156/30/20156/30/2015 8:41:07 AMAPASS
Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan t/s u/g n ok
ELE15-01922 Final6/29/20156/30/20156/29/2015 3:14:31 PMACANC
Bob Thomas Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton