Inspections for the day of: Tuesday, June 4, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01948 Electrical Rough-In6/4/20196/4/20196/4/2019 2:40:34 PMPPASS
Access is limited. Please call Jason when you arrive in the lobby.
###-#### Phone #: ###-#### Inspection requested via web by Jason Parke
North and east walls as noted on contractor print rough in ok cover.
ELE18-02369 Final6/3/20196/4/20196/4/2019 2:17:25 PMPPASS
Call Joey C. prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Final ok
ELE19-00003 Final6/4/20196/4/20196/4/2019 12:56:17 PMPPASS
Phone #: ###-#### Inspection requested via web by Terry Scott Final ok
ELE19-02027 Temporary Service6/4/20196/4/20196/4/2019 11:39:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Shaun Kirkman t/s o/h n ok
ELE19-00645 Final6/3/20196/4/20196/4/2019 10:42:23 AMAFAIL
Phone #: ###-#### Inspection requested via web by Greg Idsinga
410.16- Incandescent and LED luminaires shall not be installled with in 12" of a sorage shelf in a clothes closet. Up bed.
* Fee due- Fee charged was for service only, additional $80 due for dwelling totalling $135.
ELE19-00646 Final6/3/20196/4/20196/4/2019 10:40:23 AMAFAIL
Phone #: ###-#### Inspection requested via web by Greg Idsinga
210.8- All 15 or 20 amp 120 volt receptacle outets installed with in 6' of a sink shall have GFCI protection. Washer.
210.52(A)- No point measured along floor line shall be more than 6' from a receptacle outlet. Dining area.
210.70- A luminaire shall be installed on the exterior of each doorway with exterior access. Garage mandoor.
410.16- Incandescent and LED luminaires shall not be installed with in 12" of storage shelf in a clothes closet.
* Fee due- Fee charged was for service only, additional $80 due for dwelling totalling $135.
ELE19-02019 Electrical Rough-In6/3/20196/4/20196/4/2019 9:49:30 AMAPASS
Contact: Jason Noble Phone #: ###-#### Inspection requested via web by Deb Gooden
BCC 4-05-32 No code violation shall be retained.
394.12- Knob and tube wiring shall not be surrounded by thermo-insulation in attic.
Kitchen remodel rough in ok cover.
ELE18-01935 Electrical Rough-In6/3/20196/4/20196/4/2019 9:17:22 AMAPASS
4th floor hall drop ceiling rough-in for cover.
Contact John (Homey) McElroy
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Area noted rough in ok cover.